Bryan Boilers Triple-Flex 150 ユーザーズマニュアル

ページ / 81
 
Date:  
8-4-2010 
 
Revision: 0 
 
Form:  
2396
 
30 
 
53 
Illegal Modbus read was attempted 
54 
Safety processor brown-out reset 
occurred 
55 
Application processor watchdog reset 
occurred 
56 
Application processor brown-out reset 
occurred 
57 
Safety processor watchdog reset 
occurred 
58 
Alarm was reset by the user at the 
control 
59 
Burner control firing rate was > 
absolute max rate 
60 
Burner control firing rate was < 
absolute min rate 
61 
Burner control firing rate was invalid, 
% vs. RPM 
62 
Burner control was firing with no fan 
request 
63 
Burner control rate (nonfiring) was > 
absolute max rate 
64 
Burner control rate (nonfiring) was < 
absolute min rate 
65 
Burner control rate (nonfiring) was 
absent 
66 
Burner control rate (nonfiring) was 
invalid, % vs. RPM 
67 
Fan off cycle rate was invalid, % vs. 
RPM 
68 
Setpoint was overridden due to 
sensor fault 
69 
Modulation was overridden due to 
sensor fault 
70-74 RESERVED 
75 
Absolute max fan speed was out of 
range 
76 
Absolute min fan speed was out of 
range 
77 
Fan gain down was invalid 
78 
Fan gain up was invalid 
79 
Fan minimum duty cycle was invalid 
80 
Fan pulses per revolution was invalid 
81 
Fan PWM frequency was invalid 
82-89 RESERVED 
90 
Modulation output type was invalid 
91 
Firing rate control parameter was 
invalid 
92 
Forced rate was out of range vs. 
min/max modulation 
93 
Forced rate was invalid, % vs. RPM 
94 
Slow start ramp value was invalid 
95 
Slow start degrees value was invalid 
96 
Slow start was ended due to outlet 
sensor fault 
97 
Slow start was end due to reference 
setpoint fault 
98 
CH max modulation rate was invalid, 
% vs. RPM 
99 
CH max modulation rate was > 
absolute max rate 
100 
CH modulation range (max minus 
min) was too small (< 4% or 40 RPM) 
101 
DHW max modulation rate was 
invalid, % vs. RPM 
102 
DHW max modulation rate was > 
absolute max rate 
103 
DHW modulation range (max minus 
min) was too small (< 4% or 40 RPM) 
104 
Min modulation rate was < absolute 
min rate 
105 
Min modulation rate was invalid, % 
vs. RPM 
106 
Manual rate was invalid, % vs. RPM 
107 
Slow start enabled, but forced rate 
was invalid 
108 
Analog output hysteresis was invalid 
109 
Analog modulation output type was 
invalid 
110 
IAS open rate differential was invalid 
111 
IAS open step rate was invalid 
112-
114 
RESERVED 
115 
Fan was limited to its minimum duty 
cycle 
116 
Manual rate was > CH max 
modulation rate 
117 
Manual rate was > DHW max 
modulation rate 
118 
Manual rate was < min modulation 
rate 
119 
Manual rate in Standby was > 
absolute max rate 
120 
Modulation commanded rate was > 
CH max modulation rate 
121 
Modulation commanded rate was > 
DHW max modulation rate 
122 
Modulation commanded rate was < 
min modulation rate 
123 
Modulation rate was limited due to 
outlet limit 
124 
Modulation rate was limited due to 
Delta-T limit 
125 
Modulation rate was limited due to 
stack limit 
126 
Modulation rate was limited due to 
anti- condensation 
127 
Fan Speed out of range in RUN 
128 
Modulation rate was limited due to 
IAS was open