WARNING: 
Do not open the manual main gas cock 
(Figure 7 item 4) befo
re all pre checks, 
setups, and dry runs have been 
successfully completed. 
 
With a voltmeter check for the proper incoming 
main voltage and the proper control voltage from 
the control circuit transformer.  Refer to the 
electrical wiring diagram and boiler-rating label 
for proper voltages. 
 
Make sure the boiler is full of water and proper 
flow has been established. 
 
Power up the boiler see (paragraph 2.2.1). 
 
Navigate to the ‘Operation Screen’ (paragraph 
2.2.11).  Select the burner switch to toggle the 
burner to the off state. 
 
Navigate to the ‘Firing Rate Control Page’ 
(paragraph 2.2.14).  Select the ‘Manual in Run” 
option and enter the light off RPM from (Table 9 
Approximate Boiler Settings) in the Manua

Firing Rate box.  This will prevent the burner 
from ramping up to high fire after the flame 
stabilization period. 
 
Navigate to the ‘Annunciation Page” (paragraph 
2.2.12).  All load control inputs and interlocks 
should be in the on state with the exception of 
the air flow switch.  The air flow switch will close 
when the burner is commanded to start.  Correct 
any problem indicated.  Refer to trouble shooting 
(paragraph 0) for further help. 
 
Navigate to the ‘Operation Screen’ (paragraph 
2.2.11).  The boiler is now prepared to be placed 
in the on state by toggling the burner switch to 
on. 
2.3.4 D
RY 
R
UN
 
Navigate to the ‘Operation Screen’ (paragraph 
2.2.11).  Toggle the burner switch to on. 
 
Navigate to the ‘Status Page’ (paragraph 2.2.5).  
If there is demand for hot water the burner state 
will display driving to purge.  When the fan 
speed is within +/- 3% of the firing rate for 3 
seconds the purge timer will start and count to 
30.  After 30 seconds the fan speed is reduced 
to the light off rate.  When the fan speed is with 
in +/- 3% of the firing rate for 3 seconds the 
ignition transformer and the pilot valve are 
energized.  The pilot will light and can be 
observed from the observation port (Figure 5 
item 4).  After a duration of 5 seconds the 
ignition transformer will de-energize.  The pilot 
valve will stay energized for another 5 seconds 
before the main gas valves are energized.  
During this 10 second period the pilot should be 
djusted according to paragraph 2.3.5. 
Flame lost in Main Flame 
stablishing Period. 
 
a
 
The main gas valves will energize for 10 
seconds.  After this 10 second duration the pilot 
valve is de-energized.  The control will lockout 
with a code of 106, 
E
WARNING: 
During the first 10 seconds of this 
process the automatic gas valves 
should not have opened or been 
energized.  If any of the automatic gas 
valves are energized or open at this 
point correct the problem immediately. 
 
2.3.5 P
ILOT 
A
DJUSTMENT
 
Adjust the pilot gas pressure between 3.5 iwc 
and 4 iwc.  The pilot flame signal can be 
observed from the status page (paragraph 
2.2.5).  The minimum flame signal is .8 volts.  
The flame signal can vary between 4 volts and 
15 volts.  A flame signal closer to 15 volts is 
preferred.  Observe the pilot flame through the 
flame observation port (Figure 5 item 4).  The 
pilot should appear stable.  A stable pilot will not 
flicker on and off.  Recycle the boiler as many 
times as needed to establish a good pilot.  If the 
pilot fails to light refer to trouble shooting 
aragraph 1.1.1) for further help. 
 