Bryan Boilers Triple-Flex 150 ユーザーズマニュアル

ページ / 81
 
Date:  
8-4-2010 
 
Revision: 0 
 
Form:  
2396
 
Gas 
Manifold 
Pressure 
(IWC) 
4.4 3.6 4.0 2.0 
Max RPM 
6000-
7000 
5100-
5500 
3550-
4200 
2700-
2850 
Low Fire 
Gas 
Manifold 
Pressure 
(IWC) 
.3 .3 .2 .2 
Min RPM 
1200-
1600 
1200-
1600 
800-
950 
800-
950 
Table 9 Approximate Boiler Settings 
2.3.9 G
AS 
M
ETER 
R
EADINGS
 
Burner input rate can be checked by taking 
readings from the gas meter.  Please note 
checking the rate with a meter is the only way to 
be sure of input.  Manifold readings are only an 
approximate value and may vary from unit to 
unit. 
 
In order to obtain accurate data, there must be 
no other appliances using gas from the same 
meter while the burner input rate is being 
checked.   
 
A stopwatch or a watch with a second hand is 
required to obtain a meter reading.  Clock the 
amount of time it takes for the smallest dial to 
complete one revolution in seconds.  Use the 
following formula to obtain the cubic feet per 
hour throughput of the unit.   
 
seconds
in 
 
 time
g
clocked
 
V
gas
 
of
 
3600
c
c
1
3
=
=
=
=
ft
hr
ft
CFH
g
V
CFH
c
c
 
 
To obtain the Btu per hour throughput of the unit 
use the following formula. 
 
( )
3
-
ft
Btu 
in 
 
fuel
 
of
 
 value
heating
 
=
=
v
v
h
h
CFH
Q
 
 
If the meter is not calibrated for gas temperature 
and pressure, correction factors must be applied 
to determine correct rate in SCFH  (standard 
cubic feet per hour).  Consult the National Fuel 
Gas Code (ANSI Z223.1, NFPA 54) or the local 
gas utility for further information.  Refer to Table 
10 for corre
ction factors for the gas pressure at 
the meter.  Refer to Table 11 for the ga
temperature correction factors. 
 
Gas Pressure at Meter  Corr. Factor 
14" w.c. 
1.034 
21" w.c. 
1.051 
1 psig 
1.061 
2 psig 
1.136 
5 psig 
1.340 
Table 10 Gas Pressure Correction 
 
Gas Temp.  at Meter 
Corr. Factor 
40 
°F 
1.04 
50 
°F 
1.02 
60 
°F 
1.0 
70 
°F 
.981 
80 
°F 
.963 
90 
°F 
.945 
Table 11 Gas Temperature Correction 
 
To correct for pressure and temperature use the  
following formula. 
 
 
2.2B
 
 table
correction
 
re
 temperatu
2.2A
 
 table
correction
 
pressure
 
=
=
=
t
p
t
p
c
t
t
t
Qt
Q
38