Baseload common (i) “BL” for baseload (ii)User 
selection 0 – 100 % (d)Use existing timeout, 
Done button, and Next button functionality to 
enter these parameters. (e)User selections will 
be selected by MMI. (i) The local display does 
not adhere to the PCB (OEM parameter 
selections used by S7999). (5) In normal display 
operation the display allows a user to scroll 
through a list of temperatures with associated 
icons (CH, Inlet, Delta, DHW, Stack, Outdoor) 
using the Next button. With LL active the display 
will show the header temperature at the end of 
the list of temperatures as follows: (a)The 
characters “LL” are displayed in the number field 
(b)When the next button is pressed again the 
temperature is displayed. (c) If the Up or Down 
buttons are pressed then the LL set-point is 
changed. 5. System Display Configuration – The 
following parameters are available for OEM 
configuration and may be adjusted through a 
System Display or programmed at the OEM 
production facility. Master Sola Slave Sola LL 
frost protection enable Slave mode LL frost 
protection rate Base load rate Base load rate 
Slave sequence order LL CH demand switch LL 
Demand to firing delay LL CH set point source 
LL Modulation sensor LL Base load common LL 
Modulation backup sensor LL CH 4mA water 
temperature LL Lead selection method LL CH 
20mA water temperature LL Lag selection 
method LL Add stage method 1 LL Add stage 
detection time 1 LL Add stage error threshold LL 
Add stage rate offset LL Add stage inter-stage 
delay LL Drop stage method 1 LL Drop stage 
detection time 1 LL Drop stage error threshold 
LL Drop stage rate offset LL Lead rotation time 
LL Force lead rotation time LL Drop stage inter-
stage delay
 
 
4.5 S
LAVE 
O
PERATION 
A
ND 
S
ETUP
 
 
Slave Data Supporting Lead Lag 
 
This data is provided by each slave Sola control 
to support operation when a LL master exists. 
The illustration below summarizes the slave's 
registers and data:  
 
LL Slave 
Some slave changes relate to pump control, 
frost protection, and also are available to 3
rd 
party (non Sola) LL master devices. The generic 
LL slave is updated to operate as shown by the 
diagram below: 
 
Frost protection requests 
The frost protection in this status register will be 
set or cleared to match the status generated by 
the frost protection detection functions. 
 
Firing for local frost protection
 
This 
provides indication to the LL master that 
although the burner is firing independently, it is 
doing so for frost protection and thus is still 
available as a lead/lag slave. This is set when 1) 
frost protection is controlling the Sola per the 
priority scheme (which occurs only if frost 
protection is enabled), and 2) burner demand is 
true and the burner is currently firing or 
preparing to fire to serve that demand. 
Otherwise it will be clear. 
 
Aux Pump X, Y, and Z
 
The pump control in 
the Slave can be used by previously existing 
command devices to create the same behavior. 
However before these bits controlled actions is 
specific pump blocks, they are now more 
general. The pump X, Y, and Z bits control 
actions in any pump block defined to handle 
them (see the pump control block definition). 
 
4.6 S
LAVE 
P
ARAMETERS 
 
SLAVE ENABLE: DISABLE, ENABLE VIA 
MODBUS, ENABLE FOR SOLA MASTER 
It enables or disables the "LL Slave" Demand 
and Rate module. If the slave mode is set to 
Disable then: none of the slave functions are 
active,  Slave Status register is zero, the LL – 
Master Service Status 
register is not writable 
and is held at zero (this is important for pump 
control which might otherwise use values in this 
location). The Slave Command register is 
writable but it is mostly ignored, however the 
Aux pump X, Y, and Z are effective for any 
setting of the Slave enable parameter. The 
Enable for Sola Master 
option Slave write and 
Slave read 
parameters; if "Enable for Sola 
Master" is not selected, then these parameters 
are disabled. 
 
SLAVE MODE: USE FIRST, EQUALIZE 
RUNTIME, USE LAST  
If set to Use First, then this Sola will be used 
prior to using other Solas with other values. If 
set to Equalize Runtime, then this Sola will be 
staged according to a run time equalization 
60