Bryan Boilers Triple-Flex 150 ユーザーズマニュアル

ページ / 81
 
Date:  
8-4-2010 
 
Revision: 0 
 
Form:  
2396
 
algorithm. (Any Solas set to Use First will 
precede any that are set to Equalize Run time.)  
 
If set to Use Last, then this burner will be used 
only after all Use First and Equalize Runtime 
Solas have been brought online.  
 
SLAVE SEQUENCE ORDER: 0-255 
Slave sequence order is used to determine the 
order in which Solas will be used (staged on) for 
those Solas which the same Slave mode setting. 
Numbers may be skipped, that is 3 will be first if 
there is no 1 or 2. Note: For Equalize Runtime 
purposes, 1 does not mean the Sola will be used 
first every time; that will vary over time based on 
the master's run time equalization scheme. In 
this case the sequence number determines the 
relative order in which Sola controls will be used 
in a round-robin scheme. If the slave sequence 
number value is zero, then the slave Sola's 
ModBus address will be used instead. If two 
Solas which are set the same mode both have 
the same sequence number then an alert will 
occur and the order in which they are used will 
be arbitrary and is not guaranteed to be 
repeatable. 
 
DEMAND-TO-FIRING DELAY: MM:SS OR 
NONE  
This delay time is needed by the LL master to 
determine the length of time to wait between 
requesting a slave Sola to fire and detecting that 
it has failed to start. It should be set to the total 
time normally needed for the burner to transition 
from Standby to Run, including such things as 
transition to purge rate, prepurge time, transition 
to lightoff rate, all ignition timings, and some 
extra margin. 
 
BASE LOAD RATE: RPM OR %  
This specifies the preferred firing rate of a 
burner, which is used for some types of control 
algorithms. 
FAN DURING OFF-CYCLE RATE: RPM OR % 
(0=DISABLE)  
This determines if or where the fan is to be 
operating during the standby period.  
 
4.7 L
M
ASTER 
O
PERATION 
A
ND 
S
ETUP
 
 
LL master operation is subdivided into the 
following functions: 
•  Overall control - The LL master has 
parameters that enable and disable its 
operation. 
•  Periodic data polling - The LL master uses 
polling to discover new slave Sola devices and 
to periodically refresh the information it has 
about a known slave Sola devices. 
•  Slave control - the LL master sends each 
active slave a command and also performs a 
slave status read for each known slave device. It 
also sends a Master status broadcast that is 
heard by all slaves. 
• Slave status manager - The LL master keeps 
track of slave status for each Sola that is 
enabled as a slave device. 
•  Demand and priority - different sources of 
demand can cause the LL master to operate in 
different ways. These sources have a priority 
relationship. 
• Modulation - each demand source has one or 
more setpoints that may be active and an 
operation sensor. These are used to detect turn-
on and turn-off conditions. The difference 
between operating point and setpoint 
determines the LL master's firing rate. 
•  Stager  - the stager determines when slave 
Solas should turn on as the need for heat 
increases, and when they should turn off as the 
need for heat decreases. 
Rate allocation 
- the PID block's output is used 
to determine the firing rate of each slave Sola 
using various rate allocation techniques. 
• Add-stage methods - various methods can be 
used to determine when a new stage should be 
added. 
•  Drop-stage methods - various methods can 
be used to determine when a stage should be 
dropped 
•  Sequencer  - the Sola sequencer determines 
which Sola will be the next one to turn on or turn 
off.  
 
4.7.1 O
VERALL 
C
ONTROL
 
 
LL MASTER ENABLE: DISABLE, ENABLE, LL 
MASTER MODBUS PORT: MB1, MB2 
If 
Disable is selected then all LL master functions 
are inactive. If Enable is selected then it acts as 
the active bus master on the ModBus port it is 
assigned.  LL OPERATION SWITCH: OFF, ON 
This controls the LL master in the same way that 
the Burner switch controls a stand-alone Sola. If 
"On" then the LL master is enabled to operate. If 
this parameter is "Off" then the LL master turns 
61