Bryan Boilers AB120-W-FDGO ユーザーズマニュアル

ページ / 4
Guaranteed effi ciency and easy 
maintenance assure low cost operation
All Bryan AB Series boilers offer these operating and  performance features
Guaranteed effi ciency
The breakthrough in water tube boiler design that pro-
duced the AB Series provides operating effi ciency  so 
reliable, we guarantee it to be 83.5% for hot water boilers 
and 82% - 15 PSI / 80% - 150 PSI or better for steam.
The Bryan Flexible Tube
Bryan’s exclusive “Flexible Tube” design 
eliminates the possibility of damage 
from so-called “thermal 
shock.” Tubes are easily re-
movable and replaceable, 
without welding or rolling, 
eliminating long, expensive 
downtime should repairs 
ever be required.
Water cooled furnace
The confi guration of the 
water tubes provides a 
water cooled combustion 
chamber. A high percent-
age of the heating surface is exposed to direct radiant 
heat, increasing water velocities and heat transfer.
Large steam drum
The steam drum has generous water volume and steam 
release area. This design, along with effective drum 
internal functions, results in a stable water level and 
produces extremely dry steam at all load conditions.
Accessibility of furnace and tube area
Inner panel provides easy and complete access to fur-
nace and boiler tube area, as well as to burner head. All 
panels are heavily insulated and sealed to boiler frame. 
All access is from only one side.
Compact design, minimum fl oor space
With our compact water tube design, the overall size 
of the unit is less than most other types of boilers, yet 
maintains a full fi ve square feet of heating surface area 
Water boiler
Combination thermometer and alti-
tude gauge, ASME Code rated boiler 
relief valve, water temperature control 
(240°F max std.), high limit control, 
probe LWCO.
Steam boiler
Steam pressure gauge, steam pres-
sure control, combination low water 
cutoff and pump control, auxiliary 
low water cutoff, high limit pressure 
control, ASME-rated safety valve, 
water glass set.
Straight gas fi red unit
Electronic combustion safety con-
trol, automatic operating gas valve, 
safety gas valve, pilot solenoid valve, 
pilot ignition assembly, main manual 
gas shut-off valve, pilot cock, pilot 
and main gas pressure regulators, 
per HP. Needing only 24" for tube removal, and on only 
one side of the boiler, the AB Series boiler occupies very 
little space in the boiler room. This can result in consider-
able savings in building costs. Pressurized fi ring permits 
minimum sized breaching and vent.
Multi-pass fl ue gas travel
High velocity four-pass fl ue gas travel is obtained by a 
unique baffl ing system. This contributes to maximum fi re 
side heat transfer and overall high boiler effi ciencies.
Thermal blend water return
Bryan’s unique “thermal blend” return blends cold or 
cooler return water with warmer boiler water abridging it 
to design operating temperatures. An injector tube directs 
the “mixed” water fl ow through the downcomer to the 
lower header and heating surfaces at a temperature above 
possible condensing conditions. This reduces the possi-
bility of “cold spots” and 
damage from corrosive 
condensation.
Positive internal 
circulation
Each pass of the Bryan 
water tube slopes up-
ward. This confi guration, 
along with the large 
v o l u m e   d o w n c o m e r 
water legs, provides the 
extremely rapid natural 
thermal internal circula-
tion, promoting both high 
effi ciency of heat transfer and 
uniform temperature throughout the 
boiler. Eliminating stress damage caused 
by unequal temperature distribution is especially 
important for heating systems, particularly where inter-
mittent or continuous low temperature water returns may 
be encountered.
OPTIONAL EQUIPMENT,
EXTRA COST
1.  Manual reset high limit control
2.  Manual reset low water cutoff
3.   Auxiliary low water cutoff
4.  Combination low water cutoff 
and feeder
5.   Alarm bells or horns
6.  UL, CUL, CSD-1, FM, IRI or 
other insurance approved 
control systems
7.  Indicating lights, as desired
8.  Lead-lag systems for two or 
more boilers with or without 
outdoor reset control
9.  Draft control system
10. Low NOx package
OPTIONAL CONSTRUCTION
When ordering, please specify:
1. Boiler 
size
2.  Supply and return tempera-
tures required
3.  Boiler relief valve setting
4.  Type of fuel: natural, LP, or 
other gas and/or No. 2 oil
5.  If gas, type, BTU content, 
specifi c gravity and pressure 
available
6.  Electric power voltage, phase 
and frequency
7.  Optional extra equipment or 
construction
8.  Special approvals required 
(UL, CUL, CSD-1, FM, or IRI)
9. Altitude
Steam boiler
Optional construction to ASME Power 
Boiler Code requirements for pressure 
exceeding 150 psi to maximum of 300 
psi design pressure.
Hot water boiler
Optional construction to ASME 
Power Boiler Code requirements for 
temperatures exceeding 240°F and/or 
pressure exceeding 160 psi to maxi-
mum of 285° F operating and 300° F  
design temperature and 250 psi.
Bryan AB Series Boilers Standard and Optional Equipment
STANDARD EQUIPMENT FURNISHED
air safety switch, control panel, all 
controls installed and wired.
Straight oil fi red unit
Electronic combustion safety control, 
dual oil valves oil ignition transformer, 
two-stage fuel unit, direct spark 
ignition of oil, oil nozzle assembly, 
control panel, all controls installed 
and wired.
Combination gas-oil unit
Electronic combustion safety control, 
automatic operating gas valve, safety 
gas valve, pilot solenoid valve, pilot 
ignition assembly, main manual gas 
shut-off valve, pilot cock, pilot and 
main gas pressure regulators, air 
safety switch, manual fuel selector 
switch, dual oil valves, gas pilot for 
both fuels, two-stage fuel unit, nozzle 
assembly, control panel, all controls 
installed and wired.
Water 
Boiler
Steam  
Boiler