TABlE 1:  GAS FlOW RATE IN CUBIC FEET
 
    PER hOUR
O.
  Check limit.
1.  Adjust thermostat to highest setting.
2.  Observe temperature gauge. When temperature is 
indicated, adjust limit to setting below observed 
temperature. Main burners and pilot burner should 
extinguish, and blower should stop.
3.  Adjust limit to setting above observed temperature. 
Ignition sequence should begin.
4.  Adjust thermostat to lowest setting. Adjust limit to 
desired setting.
P.
  Adjust gas input rate to boiler.
1.  Adjust thermostat to highest setting.
2.  Check manifold gas pressure. See Table 5 or rating 
label located in the boiler’s vestibule compartment.  
Adjust gas valve pressure regulator as necessary 
(turn adjustment screw counterclockwise to 
decrease manifold pressure, or clockwise to increase 
manifold pressure). If pressure cannot be attained, 
check gas valve inlet pressure. If less than minimum 
indicated in Table 5 or boiler’s rating label, contact 
gas supplier for assistance.
3.  Clock gas meter for at least 30 seconds. Use Table 
13 to determine gas flow rate in Cubic Feet per 
Hour.
WARNING
Failure to properly adjust gas input rate will result 
in  over  firing  or  under  firing  of  the  appliance.  
Improper and unsafe boiler operation may result.
4.  Determine Input Rate. Multiply gas flow rate by gas 
heating value.
5.  Compare measured input rate to input rate stated on 
rating plate. 
a.  Boiler must not be over fired. Reduce input rate 
by decreasing manifold pressure. Do not reduce 
more than 0.3 inch w.c. If boiler is still overfired, 
contact your Burnham distributor or Regional 
Office for replacement Gas Orifice.
b.  Increase input rate if less than 98% of rating 
plate input. Increase manifold gas pressure no 
more than 0.3 inch w.c. If measured input rate is 
still less than 98% of rated input:
i.  Remove Main Burners per procedure in 
Section IX: Service.
ii.  Remove gas orifices. Drill one (1) drill size 
larger (drill size is stamped on orifice, or see 
Section X:  Repair Parts).
iii.  Reinstall gas orifices and main burners. 
Measure input rate.
6.  Recheck Main Burner Flame.
7.  Return other gas-fired appliances to previous 
conditions of use.
Q.
  Review User’s Information Manual and system 
operation with owner or operator.
Seconds 
for One 
Revolution
Size of Gas Meter Dial
One-Half 
Cu. Ft.
One
Cu. Ft.
Two
Cu. Ft.
30
60
120
240
32
56
113
225
34
53
106
212
36
50
100
200
38
47
95
189
40
45
90
180
42
43
86
172
44
41
82
164
46
39
78
157
48
37
75
150
50
36
72
144
52
35
69
138
54
33
67
133
56
32
64
129
58
31
62
124
60
30
60
120