Burnham 1100-H4 ユーザーズマニュアル

ページ / 96
7
Figure 4:  Silicone Tubing Assembly
Figure 4:  Blower Vent Connector Assembly
d.  Remove wires to Flame Roll-out Switch.
e.  Remove air diffuser screen.
f.  Remove Burner Access Panel.
g.  Mark location of Main Burner with Pilot Bracket 
on gas manifold.
h.  Hold Main Burner on throat.  Lift front of 
burners to clear orifice.  Burner which holds pilot 
can be removed by lifting the burner adjacent to 
its right first.
2.  Disconnect Vent Connector and Vent Pipe from 
Blower Outlet
3.  Remove Jacket Top Panel.  
4.  Disconnect the Black and Gary Silicone Tubing 
from the Canopy.
5.  Disconnect Wiring Harness from Blower Motor.
6.  Remove Canopy/Blower Assembly.
a.  Loosen the (4) screws from Canopy.
7.  Remove Flue Gas Baffles.  Inspect Flue Gas Baffles 
for deterioration.
8.  Inspect flue passages.  Clean with flue brush.  See 
Figure 44.
9.  Inspect heating surface in combustion chamber.  
Clean with straight handle wire brush.
10.  Install Flue Gas Baffles.
11.  Replace Canopy/Blower Assembly.
12.  Connect Silicone Tubing between Pressure Fittings 
on Canopy Assembly and Pressure Switch.  Route 
through bushings in Vestibule Panel .  See Figure 
42.
13.  Install Jacket Top Rear Panel.
14.  Connect Vent System.  See Figure 43.
15.  Connect Blower Motor Wiring Harness.
TABlE 14:  PIlOT BURNER lOCATION
Boiler Model
Main Burner with Pilot Bracket
Pilot Burner Located Between Main Burners *
SCG-3
2
2 & 3
SCG-4
3
3 & 4
SCG-5
4
4 & 5
SCG-6
5
5 & 6
SCG-7
6
6 & 7
SCG-8
7
7 & 8
SCG-9
8
8 & 9
* Main burners numbered left to right as viewed from front of boiler.