Regency FG37-LPG ユーザーズマニュアル

ページ / 32
FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater
17
INSTALLATION
 LOUVRE
INSTALLATION
Attach the top & bottom louvres to the side stove
panel using 2 screws per side.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual  shut-off  valve  during  any  pressure
testing of the gas supply piping system at test
pressures equal to or less than 1/2 psig. (3.45
kPa).    Disconnect  piping  from  valve  at  pres-
sures over 3.45 kPa.
The manifold pressure is controlled by a regu-
lator built into the gas control, and should be
checked at the pressure test point.
Note: To  properly  check  gas  pressure,
both  inlet  and  manifold  pressures
should  be  checked  using  the  valve
pressure  ports  on  the  valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen  the  "IN"  and/or  "OUT"  pressure
tap(s),  turning  counterclockwise  with  a  1/
8"  wide  flat  screwdriver.
3) Attach  manometer  to  "IN"  and/or  "OUT"
pressure  tap(s)  using  a  5/16"  (8mm)  ID
hose.
4) Light  the  pilot  and  turn  the  valve  to  "ON"
position. Read manometer.
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits specified on the safety
label.
6) When finished reading manometer, turn off
the  gas  valve,  disconnect  the  hose  and
tighten  the  screw  (clockwise)  with  a  1/8"
flat  screwdriver.  Note:  Screw  should  be
snug,  but  do  not  over  tighten
S.I.T. Valve Description
1) On-Off Solenoid Valve EV1
2) On-Off Solenoid Valve EV2
3) Inlet Pressure Test Point
4) Outlet Pressure Test Point
5) Connection  for  Pressure  Regulator/Com-
bustion Chamber Compensation
6) Pressure Regulator for Minimum and Max-
imum Outlet Pressure
7) Gas Outlet Pressure Electric Modulator
8) Pilot Outlet
9) Main Gas Outlet
10) Side Outlet