FG37 Regency Rear Flued Room Sealed Freestanding Gas Heater
FINAL CHECK
Before leaving this unit with the customer, the
installer must ensure that the appliance is firing
correctly.  This  includes:
1) Clocking the appliance to ensure the cor-
rect firing rate (rate noted on label) at 15
minutes.
2) If  required,  adjusting  the  primary  air  to
ensure that the flame does not carbon. First
allow the unit to burn for 15 min. to stabilize.
CAUTION
Any  alteration  to  the  product  that  causes
sooting  or  carboning  that  results  in  dam-
age to the exterior facia is not the respon-
sibility  of  the  manufacturer.
INSTALLATION
WIRING
CAUTION:   Label all wires prior to
disconnection when servicing con-
trols. Wiring errors can cause im-
proper and dangerous operation.
WARNING: Electrical Grounding Instructions
This appliance is equipped with a three pronged (grounding) plug for your protection against shock hazard and should be
plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.
This heater does not require a 240V A.C. supply
for  the  gas  control  to  operate.  A  240V  A.C.
power  supply  is  needed  for  the  fan/blower
operation.
Caution: Ensure that the wires do
not touch any hot surfaces and are
away from sharp edges.
OPTIONAL
REMOTE  CONTROL
Use the Regency Remote Control Kit  approved for
this  unit.  Use  of  other  systems  may  void  your
warranty.
The  remote  control  kit  comes  with  a  hand  held
transmitter and a wall mounting plate.
1) Choose  a  convenient  location  to  mount  the
hand held transmitter, protection from extreme
heat is very important.
The remote can also be used as a wall thermostat.