Ei176 DataSht RevA
 
 
 
Model 
Ei176 Optical 
Placement Information 
 
 
 
         
       
 
 
 
Alarms should be placed in accordance with the general guidelines shown in 
the diagram above. These recommendations are based on the problem of  
areas of “dead air” close to corners of rooms and apexes of ceilings, which 
could result in the prevention of smoke reaching the smoke detector 
 
 
Important Precaution: 
Do not install the actual smoke/heat 
alarm itself in new or renovated 
buildings until all work is completed 
(including floor coverings) and the 
building has been fully cleaned. 
The wiring can be installed when 
appropriate. (Excessive dust and 
debris from building work can 
contaminate the smoke chamber 
and cause problems, and it will also 
invalidate the guarantee). If it must 
be installed, cover it completely, 
particularly around the edges, with 
a dust cover (eg. a plastic bag), 
until all cleaning is finished.. 
Connect wires to the unit as in 
wiring diagram. All wiring must 
comply with local codes. 
 
 
 
Technical Specification 
 
Sensor  
Optical, uses light scatter from 
smoke 
 
Sensitivity:
 
Complies with BS 5446 Part 1: 
2000 
 
Source: 
Contains no radioactive material 
 
Airspeed:
 
Essentially immune to the effect 
 
of airspeed. 
Ambient Light:
 
Chamber housing design and 
compensation overcomes 
problems with stray light 
 
Button Test:
 
Tests strobe, vibration pad and 
panel 
Fault Monitor: 
Open/short circuit 
 
 
Supply Voltage: 
230V AC standby 8mA, alarm 
40mA 
Battery back up: 
Sealed
 
Rechargeable lead acid 
battery  
Auxiliary socket:
 
Provides 12V/200mA in alarm
 
 
 
 
 
 
 
  
 
Power-On Indicator:
   Continuous green LED 
 
Alarm:  
Xenon tube strobe (1Hz) 
 
Temperature Range:
  0 to 40°C 
 
Humidity Range:
 
0% to 90% Relative Humidity 
 
Interconnect:
 
Up to 12 interconnected 
Ei100C/105C/103C smoke/heat 
alarms 
 
Fixing:
 
Screw fixings supplied 
 
Plastic material:
 
UL94VO flame retardant 
 
Warranty:
 
5 year (limited) warranty 
 
Approvals:
 
BS 415:1990 electrical safety
 
 
Specifications are subject to change