Ei Electronics Ei146 プリント

ページ / 2
 
Shannon Free Zone, Shannon, Co. Clare, Ireland. 
Ph.
+353 61 471277   
Fx.
+353 61 471053   
 
Email.
 eielectronics@eiltd.ie
 
 
Web:
 www.eielectronics.com 
E & OE  As our policy is one of continuous product development, we reserve the right to alter product details without prior n otice
.           
Ei146 DataSht RevB
 
 
 
Model 
Ei146 Optical 
Installation & Placement 
 
Wiring for Interconnected Alarms 
 
         
       
 
 
Be very careful about correctly wiring the alarms as mixing Live and Neutral 
will blow/damage interconnected alarms. 
 
Alarms should be placed in accordance with the general guidelines shown in 
the diagram above. These recommendations are based on the problem of  
areas of “dead air” close to corners of rooms and apexes of ceilings, which 
could result in the prevention of smoke reaching the smoke detector 
 
Please consult instruction booklet for specific installation details 
Important Precaution: 
Do not install the actual smoke/heat alarm 
itself in new or renovated buildings until all 
work is completed (including floor coverings) 
and the building has been fully cleaned. The 
wiring can be installed when appropriate. 
(Excessive dust and debris from building work 
can contaminate the smoke chamber and 
cause problems, and it will also invalidate the 
guarantee). If it must be installed, cover it 
completely, particularly around the edges, with 
a dust cover (eg. a plastic bag), until all 
cleaning is finished.. Connect wires to the unit 
as in wiring diagram. All wiring must comply 
with local codes. 
 
 
 
 
Technical Specification 
Sensor  
Optical, uses light scatter from 
smoke 
 
Sensitivity:
 
Complies with BS 5446 Part 1: 
2000 
 
Source: 
Contains no radioactive material 
 
Airspeed:
 
Essentially immune to the effect 
 
of airspeed. 
 
Button Test:
 
Simulates the effect of smoke and 
checks chamber, electronics and 
horn. 
 
Ambient Light:
 
Chamber housing design and  
compensation overcomes 
problems with stray light. 
 
AutomaticSelf-Test:
 
Smoke Chamber is tested every 40 
 
Sec. and unit beeps (without LED 
 
flash) if it is degraded. 
 
Insect Screen:
 
Prevents insects or debris entering  
chamber (1.00mm mesh size) 
 
Supply Voltage: 
230V AC 
 
Battery back up: 
9V Alkaline Battery 
 
 
Specifications are subject to change
 
 
 
 
 
 
 
  
Power-On Indicator:
   Continuous green LED 
 
Alarm:  
Electronic Piezoelectric horn 
 
Alarm Sound Output:
  85dB (minimum) at 3m 
 
Alarm Status:
 
Red LED flashes every second on 
 
unit sensing fire 
 
Temperature Range:
  0° to 40°C 
 
Humidity Range:
 
15% to 95% Relative Humidity 
 
Interconnect:
 
Up to 12 interconnected mains 
powered easi-fit smoke or heat 
alarms, along with an EI128 relay 
base 
 
Fixing:
 
Easi-Fit mounting base 
 
Plastic material:
 
UL94VO flame retardant 
 
Dimensions: 
152mm x 50mm depth
 
 
Weight: 
345g 
 
Warranty:
 
5 year (limited) warranty 
 
Approvals:
 
Kitemarked to BS EN 14604:2005, 
CE Approved