T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
5
63-4355—4
INSTALLATION
When Installing this Product…
1.
Read these instructions carefully. Failure to follow 
the instructions can damage the product or cause a 
hazardous condition.
2.
Check the ratings given in the instructions and on the 
product to make sure the product is suitable for your 
application.
3.
Installer must be a trained, experienced service 
technician.
4.
After completing installation, use these instructions to 
check out the product operation.
Location
Do not install the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall behind 
the thermostat.
T7200 Wallplate or Q7300 Subbase without 
Remote-Mounted Temperature Sensor
Install the thermostat about 5 ft (1.5m) above the floor in 
an area with good air circulation at average temperature. 
See Fig. 2.
Q7300 Subbase with Remote-Mounted 
Temperature Sensor(s)
If only the remote-mounted temperature sensor(s) is used 
to sense and control room temperature, then install the 
thermostat in an area that is accessible for setting and 
adjusting the temperature and settings.
If both the subbase and remote-mounted temperature 
sensor(s) are used to sense and control room temperature, 
then install the subbase about 5 ft above the floor in an area 
with good air circulation.
Install the remote-mounted sensor(s) about 5 ft (1.5m) above 
the floor in an area with good air circulation at average 
temperature. See Fig. 2.
If multiple remote sensors are required, they must be 
arranged in a temperature averaging network consisting of 
two, three, four, five or nine sensors. See Fig. 3 through 8.
NOTES:
— When sensor averaging, the T7147A can be substituted 
for the T7047C. The T7147A includes OVERRIDE and 
WARMER/COOLER keys.
— Up to four T7147As can be used in parallel to place the 
thermostat in Temporary Occupied.
Fig. 2. Typical location of thermostat 
or remote-mounted sensor.
IMPORTANT
To avoid electrical interference, which can cause 
erratic performances, keep wiring runs as short as 
possible and do not run thermostat wires adjacent to 
the line voltage electrical distribution systems. Use 
shielded cable (Belden type 8762 or equivalent for 
2-wire and Belden type 8772 or equivalent for 
3-wire). The cable shield must be grounded only at 
the controlled equipment case.
Fig. 3. One T7047C Sensor providing temperature 
sensing for T7300/Q7300 Thermostat/Subbase.
Fig. 4. Two T7047G Sensors providing temperature 
averaging network for T7300/Q7300 Thermostat/Subbase.
5 FEET
(1.5 METERS)
YES
NO
NO
NO
M4823A
M4839BB
T
T
SUBBASE
T
T
T7047C
M4838
T
T
SUBBASE
T
T
T7047G
T7047G
T
T