VisionPRO® IAQ 
 
69-1816EFS—03
  0210 
External fossil 
fuel kit
1
 
External fossil fuel kit controls backup heat
0
 
Thermostat controls backup heat (outdoor sensor required)
  0220 
Stage 1 compressor 
1cycle rate
E
 
Auto Discover 
**
 
[Other options: 1 to CPH]
  0230 
Stage 2 compressor 
cycle rate
E
 
Auto Discover 
**
 
[Other options: 1 to 6 CPH]
  0240 
Stage 1 heat cycle 
rate (CPH= cycles 
per hour)
E
 
Auto Discover 
**
 
[Other options: 1 to 12 CPH]
  0250 
Stage 2 stage heat 
cycle rate (CPH)
E
 
Auto Discover 
**
 
[Other options: 1 to 12 CPH]
  0260 
Stage 3 heat cycle 
rate (CPH)
E
 
Auto Discover 
**
 
[Other options: 1 to 12 CPH]
  0280 
Backlight
0
 
Backlight on for approx. 45 seconds after keypress
1
 
Backlight always on low intensity, full bright after keypress
  0300 
Manual/Auto 
changeover
0
 
Manual (User options: Heat/Cool/Off)
1
 
Automatic (User options: Heat/Cool/Auto/Off)
 
(System selects heat/cool based on indoor temp.)
  0310 
Auto changeover 
deadband
3
 
Heat/cool settings 3°F apart (1.5°C)
 
[Other options: 2-9 (2°F to 9°F/1°C to 5°C)]
  0320 
Temperature display 0
 
Fahrenheit
1
 
Celsius
  0330 
Daylight savings
Auto-change to daylight savings time (2007 and beyond, for 
areas that use the new 2007 DST calendar)
Auto-change to daylight savings time (through 2006, and for areas 
that do not use the new 2007 DST calendar)
Daylight savings time is turned off
  0340 
Indoor temp. 
sensor
0
 
Display temp. at thermostat location only
Display temp. at indoor sensor location(s)
Average between thermostat & sensor location(s)
  0342 
Outdoor temp. 
sensor
E
 
Auto Discover 
**
None
Remote sensor
  0345 
Dual fuel heat 
pump control
1
 
Balance point plus 2°F droop 
**
Balance point only 
**
Balance point/Aux Heat Lockout plus 2°F droop 
**
  0346 
Dual fuel heat 
pump upstage to 
furnace timer
60
 
60 minutes 
**
Off
 
[Other options: 30, 45 or 75 minutes]
  0350 
Heat pump 
compressor lockout
0
 
No compressor lockout 
**
 
[Other options: 5 to 60°F (-15°C to 15.5°C)]
  0360 
Heat pump 
auxiliary lockout
0
 
No heat pump auxiliary lockout 
**
 
[Other options: 5 to 65°F (-15°C to 18.5°C)]
  0365 
Discharge temp. 
sensor
E
 
Auto Discover 
**
No
Yes
  0370 
Indoor humidity 
sensor
1
 
Internal sensor in thermostat
Sensors disabled
Auto Discover 
**
Setup function 
Settings & options (factory default in bold)
Installer setup
**See page 6