Honeywell IAQ ユーザーズマニュアル

ページ / 24
Installation Guide
69-1816EFS—03 
**See page 6
  0372 
Indoor humidifica-
tion control
E
 
Auto Discover 
**
Off
Humidify (no frost protection)
Humidify (with frost protection)
  0374 
Humidifier fan action 0
 
Humidify only while fan or heat is on
Humidify forces fan on
Humidify only when heat is on
Humidifier operates independent of fan
  0379 
Dehumidification 
control
No dehumidification control
Dehumidify with air conditioner
Whole house dehumidifier
  0383 
Over-cooling limit
3°F (1.5°C)
 
[Other options: 1, 2 (1°F or 2°F/0.5°C to 1.5°C)]
  0384 
Dehumidification 
fan action
System fan turns on with dehumidifier
Dehumidifier operates independent of fan
  0390 
Dehumidification 
away mode
No
Yes
  0391 
Dehum. away mode 
fan setting
Fan auto
Fan always on
Fan circulate
  0392 
Dehum. away mode 
low limit temp.
76  Low limit temperature 76°F (24°C)
 
[Other options: 70°F to 80°F (21°C to 27°C)]
  0393 
Dehum. away mode 
temp. setting
85  Away temperature 85°F (29°C)
 
[Other options: 70°F to 99°F (21°C to 37°C)]
  0394 
Away dehumidifica-
tion setting
65  Away humidity level 65%
 
[Other options: 55% to 70%]
  0400 
Ventilation control
No ventilation
Ventilation always allowed
Ventilation not allowed during sleep period
  0401 
Number of 
bedrooms
Two bedrooms
 
[Other options: 1 to 6]
  0402 
Size of house
10  1,000 square feet
 
[Other options: 11 to 50 (1,100 to 5,000 square feet)]
  0403 
Ventilation level
160  CFM (cubic feet per minute)
 
[Other options: (30 to 195 CFM)]
  0404 
Max. ventilation 
% limit
50  50% ventilation limit
 
[Other options: 30% to 60% or 100%]
P 
Meets ASHRAE 62.2 standard
F 
Does not meet ASHRAE 62.2 standard
  0405 
Ventilation fan 
action
Ventilation on forces fan on
Ventilation does not force fan on
  0406 
Ventilation in high 
humidity
On (heat mode only)
Off
  0500 
Furnace filter 
change alert
Auto Discover 
**
 
270-day run time
Off 
365-day run time
10-day run time 
30 calendar days
30-day run time 
10  60 calendar days
60-day run time 
11  90 calendar days
90-day run time 
12  120 calendar days
120-day run time 
13  180 calendar days
180-day run time 
14  365 calendar days
Setup function 
Settings & options (factory default in bold)
Installer setup