American Water Heater (A)BCG38T500-8P ユーザーズマニュアル

ページ / 40
19
Servicing should only be performed by a Qualifi ed Service Agent
OPERATION AND SERVICE
BLOWER PROVER SWITCH - SETTINGS
Vent Connection
Exhaust/Outlet
Blower Prover Switch
Blower (Draft Inducer)
Optional Hot Water Outlet
Figure 15
Table 4
BLOWER PROVER SWITCH TABLE
Model
Pressure Setting to Close Switch (Inches W.C.)
(A)BCG385T500-8N/8P
-2.85” ± 0.13”
NOTE: The Blower Prover Switch contacts are normally open and will close on a fall in    
 
pressure.  This will be a negative pressure (i.e., a vacuum).