Servicing should only be performed by a Qualifi ed Service Agent
TROUBLESHOOTING
4   Check molex plug connector between igniter/flame sensor assembly and control board; 
Also check flame sense (12 pin) plug connection at control board.
8 FLASHES
Igniter not sensed and/or water heater not grounded.
1   Test igniter resistance.  It should should be 11 - 20 ohms. Replace igniter if open 
continuity.
2   Ensure that the water heater is grounded. Check all ground wires on heater and 
controls.
3   Check molex plug connector between igniter/flame sensor assembly and control board.  
Also check igniter (4 pin) plug connection at control board.
CONTINUOUS FLASH
Flame sensed out of sequence; continuous flame sensed for more than 5 seconds 
without gas valve being energized.
  
1   Ensure that the gas valve is not failing to close at the end of the heating cycle.
CONTINUOUS ON
Internal control board failure. 
1   Replace ignition control board.