page 20 — MaYCO LS600p CONCReTe pUMp • OpeRaTiON MaNUaL — Rev. #0 (05/13/13) 
Reverse Pumping Procedure
1.  Switch the pump into reverse.  With pump speed at a 
medium-slow (approx. 12 strokes per min.) try to pull 
the “pack” back into the hopper with 5 or 6 reverse 
strokes. 
2.  Remix the concrete in the hopper.
3.  Switch the pump into forward. If it is still plugged, repeat 
“Reversing” procedure three times. 
4.  If concrete still does not move, proceed to the Shuttle 
Tube Inspection Procedure.
Shuttle Tube inspection procedure
1.  Stop the pump. Turn off the engine.
2.  The senior or most experienced operator must warn all 
others to stand at least 20 feet away from the machine 
and turn their heads to face away from the pump.
3.  The operator will position himself beside the reducing 
elbow at the pump outlet.  Wearing safety glasses, slip 
the end of a pry bar (24" length of reinforcing steel rod) 
under the latch of the hose clamp and flip it up.
4.  Carefully knock the end of the hose away from the 
reducer.
5.  Chip the concrete out of the reducer with the pry bar. 
  DANGER
Accumulator Pressure
Make sure the accumulator pressure 
gauge reads 
ZERO psi. prior to 
performing any maintenance or 
inspection.You must follow lock 
out-tag out procedures. Improper 
accumulator pressure can result in 
an explosion causing serious injury 
or 
death.
GEnERAL InfORMAtIOn
6.  Remove the reducer.  From the discharge end, chip 
the concrete out of the shuttle tube with the pry-bar. 
If concrete cannot be loosened from the outlet of the 
shuttle tube, remove the clean-out plug on the bottom 
of the hopper to discharge the concrete.
7.  Chip the blockage out with the pry-bar.
8.  Flush the shuttle tube with water.
9.  Before resuming operation of the pump, perform the 
“Reverse” Pumping Procedure to relieve pressure on 
the shuttle tubes.