9.2 Error Code and Error Message List
9 - 5
9
E
RROR CODES
 AND 
E
RROR ME
SSAGES
APPE
NDICES
INDEX
Error 
Code
Error Message
Definition
Action
423
Information is insufficient in net-
work table
The station number set as the screen data does 
not exist in the Ethernet setting of GT Designer/ GT 
Designer 2.
Add the station number set as the screen data to 
the Ethernet setting of GT Designer/GT Designer 
2.
(Use the station number of the PLC side Ethernet 
module set in the parameter setting of GX Devel-
oper.)
424
The same bureau is set by GOT 
and monitor data.
The station number set on the utility screen of the 
GOT is the same as the station number set in the 
Ethernet setting of GT Designer/GT Designer 2 
(station number of the PLC side Ethernet module) 
or the station number set as the screen data.
Check the following data and do not use the same 
station number.
1. Check the station number of the GOT on the util-
ity screen of the GOT.
2. Check the station number set as the screen 
data.
3. Check the station number set in the Ethernet 
setting.
(Use the station number of the PLC side Ether-
net module set in the parameter setting of GX 
Developer.)
448
Devices outside file register and 
other ranges included
Devices specified are outside file register or buffer 
memory range of QnACPU
Set PLC file registers. Also correct monitor devices
470
Communication destination 
faulty
During monitoring of the other station via 
MELSECNET/10, a fault occurred in the corre-
sponding communication station
Check whether the corresponding communication 
station has been set correctly in the management 
station (reconsider the parameters, switch setting, 
etc.)
499
CPU communication error
Other communication error
Check for any disconnected cable or improperly fit-
ted communication module