Mitsubishi Electronics A951GOT ユーザーズマニュアル

ページ / 124
9.2 Error Code and Error Message List
9 - 3
9
E
RROR CODES
 AND 
E
RROR ME
SSAGES
APPE
NDICES
INDEX
Error 
Code
Error Message
Definition
Action
321
Unauthorized station number 
specified for monitor device
The station number specified as a monitor destina-
tion does not exist or is not the station to be moni-
tored
Confirm the monitor destination station number in 
the screen data
322
Specified device outside range
The device number to be monitored is outside the 
permissible range of the corresponding PLC CPU
Set the monitored PLC CPU and parameters to set 
the device in the monitorable range
323
Specified file register outside 
range
324
AD51H-dedicated device used 
without AD51H
The AD51H-dedicated device was monitored in the 
system which does not use the AD51H
Incorporate the AD51H into the system or stop 
monitoring of the AD51H-dedicated device
325
Specified special module not 
loaded
The specified special module is not loaded
Check the loading status of the specified special 
module
330
PC card capacity short
The PC card does not have enough capacity
Check the capacity
331
PC card not loaded or memory 
card access switch OFF
The PC card is not loaded or the memory card 
access switch is OFF
1. Load the PC card
2. Turn ON the access switch
332
Format error
The PC card is not formatted
Format the PC card
333
PC card write-protected to dis-
able write
The PC card is write-protected
Make the PC card write-enabled
334
PC card fault
PC card failure
Change the PC card
335
PC card battery voltage low
The battery voltage of the PC card is low
Change the battery of the PC card
340
Printer in error or power off
The printer is faulty or its power is not on
1. Check the printer
2. The Printer switch it on
341
Printer fault
342
The fuse of KBF module was 
blown
A fault occurred in the external I/O interface mod-
ule.
1. If external power (24VDC) is not supplied, sup-
ply external power.
2. If external power is supplied, change the exter-
nal I/O interface module.
343
KBF module status is abnormal
The external I/O interface module is not mounted 
properly.
Mount the external I/O interface module properly.
345
BCD/BIN conversion error
It has been attempted to display/enter a value that 
cannot be BCD/BIN converted
1. Change the device data to be displayed into a 
BCD value
2. Enter the value of 4-digit integer
350
RS-232C communication error
The cable used to connect the GOT and personal 
computer is faulty
1. Check for an unplugged communication cable 
connector
2. check the cables used
351
Recipe file abnormal
Recipe file data are not normal
1. Check recipe file data in PC card
2. Start GOT after deleting recipe file in PC card
352
Recipe file generation error
Recipe file generation failed
Start GOT after loading PC card
353
Recipe file write disabled
Data write to recipe file failed
1. Check write protect of PC card
2. Check PC card capacity
3. Do not unload PC card during recipe operation
354
Error during recipe file write
Error occurred during recipe file write
Do not unload PC card during recipe operation
355
Error during recipe file read
Error occurred during recipe file read
1. Do not unload PC card during recipe operation
2. Check recipe file data (device values) in PC card