11. TROUBLESHOOTING
11.4.2 Remedies for alarms
CAUTION
When any alarm has occurred, eliminate its cause, ensure safety, then reset the
alarm, and restart operation. Otherwise, injury may occur.
alarm, and restart operation. Otherwise, injury may occur.
If an absolute position erase (A25) occurred, always make home position setting
again. Not doing so may cause unexpected operation.
again. Not doing so may cause unexpected operation.
As soon as an alarm occurs, turn off Servo-on (RYn0) and power off.
POINT
When any of the following alarms has occurred, do not deactivate the alarm
and resume operation repeatedly. To do so will cause the servo amplifier/servo
motor to fail. Remove the cause of occurrence, and leave a cooling time of
more than 30 minutes before resuming operation.
and resume operation repeatedly. To do so will cause the servo amplifier/servo
motor to fail. Remove the cause of occurrence, and leave a cooling time of
more than 30 minutes before resuming operation.
Regenerative error (A30)
Overload 1 (A50)
Overload 2 (A51)
For the alarm deactivation method, refer to section 11.4.1.
When an alarm occurs, the trouble (ALM) switches off and the dynamic brake is operated to stop the servo
motor. At this time, the display indicates the alarm No.
The servo motor comes to a stop. Remove the cause of the alarm in accordance with this section. Use the MR
Configurator to refer to a factor of alarm occurrence.
Display Name
Definition
Cause
Action
1. Power supply voltage is low.
2. There was an instantaneous control
2. There was an instantaneous control
power failure of 60ms or longer.
3. Shortage of power supply capacity
caused the power supply voltage to
drop at start, etc.
drop at start, etc.
4. The bus voltage dropped to the
following value or less.
MR-J3- T: 200VDC
MR-J3- T1: 158VDC
MR-J3- T4: 380VDC
MR-J3- T: 200VDC
MR-J3- T1: 158VDC
MR-J3- T4: 380VDC
Check the power supply.
A10 Undervoltage Power
supply
voltage dropped.
MR-J3- T:
160VAC or less
MR-J3- T1:
83VAC or less
MR-J3- T4:
280VAC or less
MR-J3- T:
160VAC or less
MR-J3- T1:
83VAC or less
MR-J3- T4:
280VAC or less
5. Faulty parts in the servo amplifier.
Checking method
Alarm (A10) occurs if power is
switched on after disconnection
of all cables but the control
circuit power supply cables.
switched on after disconnection
of all cables but the control
circuit power supply cables.
Change the servo amplifier.
A12 Memory
error
1
(RAM)
RAM, memory fault
A13
Clock error
Printed board fault
Faulty parts in the servo amplifier.
Checking method
Alarm (any of A12 and A13)
occurs if power is switched on
after disconnection of all cables
but the control circuit power
supply cables.
occurs if power is switched on
after disconnection of all cables
but the control circuit power
supply cables.
Change the servo amplifier.