Page 151
IP Service Ports
Connect to the following TCP/IP Service Ports for communications over Ethernet.
1
  EtherGate communications are available only through COM2. This feature is available only on 
9330 and 9350 meters.
Profibus Port
This option is offered exclusively on the 9300 meter.
N
OTE
The Profibus Master file (.GSD file) is included on a floppy disk with the meter. This file must be installed
on your Profibus Masters before the meter can communicate with the Profibus network.
The optional Profibus port on the meter is capable of operating baud rates up to 12 
Mbps. Profibus Connections to the meter are made via the nine-pin connector on 
the rear of the unit. Plug your Profibus connector from the network into this 
connector.
Protocol
TCP/IP Port
ION
7700
Modbus RTU
7701
Modbus/TCP
502
EtherGate 
1
7802
PROFIBUS
DE
PWR
LEDs (DE and PWR)
Profibus female 