Mitsubishi Electronics A800 ユーザーズマニュアル

ページ / 116
Connection of motor with encoder (vector control)
55
2
Instructions for encoder cable wiring
 • Use shielded twisted pair cables (0.2 mm
2
 or larger) to connect the FR-A8AP. For the wiring to the terminals PG and SD, 
use several cables in parallel or use a thick cable, according to the wiring length.
To protect the cables from noise, run them away from any source of noise (such as the main circuit and power supply 
voltage).

When differential line driver is set and a wiring length is 30 m or more.
The wiring length can be extended to 100 m by increasing the 5 V power supply (approximately to 5.5 V) while using six or more 0.2 mm
2
 gauge 
cables in parallel or a 1.25 mm
2
 or larger gauge cable. The voltage applied must be within power supply specifications of encoder.
 • To reduce noise of the encoder cable, earth (ground) the encoder's shielded cable to the enclosure
(as close as possible to the inverter) with a P-clip or U-clip made of metal.
 • When one encoder is shared between FR-A8AP and CNC (computerized numerical controller), its output signal should be 
connected as shown below. In this case, the wiring length between FR-A8AP and CNC should be as short as possible, 
within 5 m.
NOTE
 • For the details of the optional encoder dedicated cable (FR-JCBL/FR-V7CBL), refer to 
.
 • The FR-V7CBL is provided with a P-clip for earthing (grounding) shielded cables.
Wiring length
Parallel connection
Larger-size cable
Within 10 m
At least two cables in parallel
Cable gauge 0.2 mm
2
0.4 mm
2
 or larger
Within 20 m
At least four cables in parallel
0.75 mm
2
 or larger
Within 100 m
At least six cables in parallel
1.25 mm
2
 or larger
PZ2
PZ1
PA1
PA2
FB1
FB2
SD
PG
G
F
D
C
B
A
R
S
Encoder
2 mm
2
FR-A800
(FR-A8AP)
Example of parallel connection
with two cables
(with complementary encoder output)
Encoder cable
Shield
P-clip
Earthing (grounding) example using a P-clip
NC
Maximum 5 m
(two parallel cables)
Inverter
(FR-A8AP)
Encoder