Sharp JW-20FLT ユーザーズマニュアル

ページ / 224
4-3
                              
Chapter 4: Name and Function of Each Part
4
4-3 Z-336J
2
1
O
F
F
  SWA 
ON   
SW1
SW1
SWA
SW6
ON
8 9
0
1
23
4
5
6
7
SW6
ON
S0
S1 
S2 
S3 
S4 
S5 
S6 
S7 
HE 
PE 
 
  T 
12V 
RX 
TX 
LN
S0
S1 
S2 
S3 
S4 
S5 
S6 
S7 
HE 
PE 
 
 
12V 
RX 
TX 
LN
2
1
F
3
2
1
F
FG
0V
12V
 
1
Display panel
2
Connector for programmer
4
Connector for 10BASE5
6
12 VDC power supply input terminal
8
Reset switch
7
Module No. switch SW4
(Factory setting: 0)
9
Switch SWA
0
Switch SW1
5
Switch SW6
3
Connector for 10BASE-T
(Factory setting: ON)
Factory setting
: ON
Factory setting
: ON
Name
Function
1
Display panel
Displays this board operating status using LEDs.
LN
Lights when communicating normally.
TX
Blink at transmitting data.
RX
Blink at receiving data.
12 V
Lights when 12 VDC is supplied. (Only when 10BASE5 is used.)
T
Lights at test mode. (Normally, this is not used.)
PE
Lights at parameter setting error.
HE
Lights at this board error.
S0 to S7
Displays the station number when operating normally. Displays an error
code if an error occurs.
2
Connector for programmer
Connect a JW-14PG programmer or similar equipment to set the
parameters on this board.
3
Connector for 10BASE-T
Connect the 10BASE-T coaxial cable.
4
Connector for 10BASE5
Connect the 10BASE5 coaxial cable.
Make sure to slide the lock securely to the "lock" position.
5
Switch SW6
ON
The shield on the cable between a 10BASE-T connector and a
10BASE5 connector and the FG (base) on this module will be shorted
together.
OFF
The shield on the cable between a 10BASE-T connector and a
10BASE5 connector is not shorted to the base.
- Ground the FG line on the 12 VDC connector separately.
6
12 VDC power supply
input terminal
When 10BASE5 is used, connect a commercially available DC power
supply that is designed to supply power to transceivers. The DC power
supply must provide 12VDC ±5% and 0.5 A or more.
7
Module No. switch
Specify a module number from 0 to 6.
- Be careful do not use the same number for another option board.
8
Reset switch
Only used by SHARP engineers. Users should not press this switch.
9
Number of communication
boards
Switch SWA
Specify the number of communication boards actually installed
(including the Z-336J).
-
See pages 5-3 to 5-7.
0
Switch SW1
No need to set this switch for the Z-336J. (Always set to OFF (default).)