Cheetah NS 10K.2 SAS Product Manual, Rev. C
6.4
Environmental limits
Temperature and humidity values experienced by the drive must be such that condensation does not occur on 
any drive part. Altitude and atmospheric pressure specifications are referenced to a standard day at 58.7°F 
(14.8°C). Maximum wet bulb temperature is 82°F (28°C).
6.4.1
Temperature
a. Operating
The maximum allowable continuous or sustained HDA case temperature for the rated Annualized Failure 
Rate (AFR) is 122°F (50°C) The maximum allowable HDA case temperature is 60°C. Occasional excur-
sions of HDA case temperatures above 122°F (50°C) or below 41°F (5°C) may occur without impact to 
specified AFR. Continual or sustained operation at HDA case temperatures outside these limits may 
degrade AFR.
Provided the HDA case temperatures limits are met, the drive meets all specifications over a 41°F to 131°F 
(5°C to 55°C) drive ambient temperature range with a maximum temperature gradient of 86°F (30°C) per 
hour. Air flow may be needed in the drive enclosure to keep within this range (see Section 8.3). Operation at 
HDA case temperatures outside this range may adversely affect the drives ability to meet specifications. To 
confirm that the required cooling for the electronics and HDA case is provided, place the drive in its final 
mechanical configuration, perform random write/read operations and measure the HDA case temperature 
after it has stabilized.
b. Non-operating
–40° to 158°F (–40° to 70°C) package ambient with a maximum gradient of 86°F (30°C) per hour. This 
specification assumes that the drive is packaged in the shipping container designed by Seagate for use with 
drive.  
HDA Temp.
Check Point
.5"
1.0"
    
Figure 5. 
Location of the HDA temperature check point