Siemens PCS7 ユーザーズマニュアル

ページ / 21
Product Information
PCS7/TM V2.02
24.10.2001
 Siemens AG 2001
4 of 21
terminated.
 
Switchover of the Servers after CS 275 Coupling Fault
When at least one connection to a subsidiary AS fails the multi-clients switch over to the redun-
dant server. Attention ! An intentional switch off of a connection (AS) causes the same effect.
To activate these functions it is necessary to make an entry in the registry of the servers. This entry
can be made by double-clicking on the file Fault_ein.reg.
Double-clicking on the file Fault_aus.reg cancels this function.
Both files are stored in the CD directory <...>\PCS7_Version_5\Redundancy.
 
Channel Diagnosis
Hence the TELEPERM M Channel DLL uses the WinCC Channel Diagnosis. It is initiated via
\Simatic\WinCC\Tools\Channel Diagnosis. You should select the following basic configuration:
2.2.2 Restrictions
 Trends by Means of Measurement Points (function of WinCC-LTO)
This function will no longer be available from V5.0 onwards.
  Creating the WinCC Tag Management
The WinCC Tag Management (variable under connections) may solely be created via "TELEPERM
M Import blocks" wizard provided.
  Order of Simultaneously Occurring Messages in Alarm Logging
Simultaneously occurring messages of a function block (alarm, warning, tolerance) are given out in
order of the message numbers (WinCC system feature).
2.3  PCS7/TM-OCX (NORA) (formerly: WinCC/TM-OCX (NORA))
 
2.3.1 
Modifications vs. Version V2.01
In addition to the present image blocks in TELEPERM M NORA representation we deliver a set of
renovated image blocks. They have identical display with the present ones, additionally they are sup-
plemented with the properties “Modus” (display mode group/ loop), “Farbe_*” (color of bars and digital
values). For details see description “TELEPERM NORA renoviert.pdf”. The contractions G_ or K_ in
the OCX names have been dropped.