Delta Tau 5xx-603869-xUxx ユーザーズマニュアル

ページ / 50
Brick Motion Controller Hardware Reference Manual 
 
System Wiring
 
21 
J8:  Extra General Purpose I/O (Optional) 
General purpose I/O is available on the Brick Motion Controller.  All I/O is electrically isolated from the 
drive.  Inputs can be configured for sinking or sourcing applications. All Inputs are 12-24VDC. All 
Outputs are 24V nominal operation, 0.5A maximum current.  Outputs are robust against ESD and 
overload. 
J8 General Purpose I/O 
(Female DB-37 Connector) 
36
33
1
20
2
3
4
5
9
10
28
27
26
25
24
21
22
23
11
8
7
6
29
30
32
16
15
14
13
12
17
18
19
31
34
35
37
 
Pin # 
Symbol 
Function 
Description 
1 GPIN33  Input 
Input 
33 
2 GPIN35  Input 
Input 
35 
3 GPIN37  Input 
Input 
37 
4 GPIN39  Input 
Input 
39 
5 GPIN41  Input 
Input 
41 
6 GPIN43  Input 
Input 
43 
7 GPIN45  Input 
Input 
45 
8 GPIN47  Input 
Input 
47 
IN_COM 33-40 
Input 
Input 33 to 40 Common 
10 N.C 
 
Not 
Connected 
11 
COM_EMT 
Input 
Common Emitter * 
12 
GP17- 
Output 
Sourcing Output 17 ** 
13 
GP18- 
Output 
Sourcing Output 18 ** 
14 
GP19- 
Output 
Sourcing Output 19 ** 
15 
GP20- 
Output 
Sourcing Output 20 ** 
16 
GP21- 
Output 
Sourcing Output 21 ** 
17 
GP22- 
Output 
Sourcing Output 22 ** 
18 
GP23- 
Output 
Sourcing Output 23 ** 
19 
GP24- 
Output 
Sourcing Output 24 ** 
20 GPIN34  Input 
Input 
34 
21 GPIN36  Input 
Input 
36 
22 GPIN38  Input 
Input 
38 
23 GPIN40  Input 
Input 
40 
24 GPIN42  Input 
Input 
42 
25 GPIN44  Input 
Input 
44 
26 GPIN46  Input 
Input 
46 
27 GPIN48  Input 
Input 
48 
28 
IN_COM_41-48 
Input 
Input 41 to 48 Common 
29 COM_COL  Input 
Common Collector ** 
30 
GP17+ 
Output 
Sinking Output 17 * 
31 
GP18+ 
Output 
Sinking Output 18 * 
32 
GP19+ 
Output 
Sinking Output 19 * 
33 
GP20+ 
Output 
Sinking Output 20 *
 
34 
GP05+ 
Output 
Sinking Output 21 * 
35 
GP22+ 
Output 
Sinking Output 22 * 
36 
GP23+ 
Output 
Sinking Output 23 * 
37 
GP24+ 
Output 
Sinking Output 24 * 
*For sinking outputs, connect the COM_EMT (pin11) line to the Analog Ground of the Power supply and the outputs to 
the individual plus output lines, e.g. GPO1+ 
**For sourcing outputs, connect the COM_COL (pin29) line to 12-24V and the outputs to the individual minus output 
lines, e.g., GPO1- 
Do not mix topologies, i.e., all sinking or all sourcing outputs.  If the common emitter is used, the common collector 