Delta Tau 5xx-603869-xUxx ユーザーズマニュアル

ページ / 50
 
Brick Motion Controller Hardware Reference Manual 
22
 
System Wiring
 
Suggested M-Variable Addressing for the General Purpose I/O (J8) 
Suggested M-var. # 
Address 
Notes 
M64-> 
Y:$78A00,0,1 
Input 33 Data Line, J6 Pin 1 
M65-> 
Y:$78A00,1,1 
Input 34 Data Line, J6 Pin 20 
M66-> 
Y:$78A00,2,1 
Input 35 Data Line, J6 Pin 2 
M67-> 
Y:$78A00,3,1 
Input 36 Data Line, J6 Pin 21 
M68-> 
Y:$78A00,4,1 
Input 37 Data Line, J6 Pin 3 
M69-> 
Y:$78A00,5,1 
Input 38 Data Line, J6 Pin 22 
M70-> 
Y:$78A00,6,1 
Input 39 Data Line, J6 Pin 4 
M71-> 
Y:$78A00,7,1 
Input 40 Data Line, J6 Pin 23 
M72-> 
Y:$78A01,0,1 
Input 41 Data Line, J6 Pin 5 
M73-> 
Y:$78A01,1,1 
Input 42 Data Line, J6 Pin 24 
M74-> 
Y:$78A01,2,1 
Input 43 Data Line, J6 Pin 6 
M75-> 
Y:$78A01,3,1 
Input 44 Data Line, J6 Pin 25 
M76-> 
Y:$78A01,4,1 
Input 45 Data Line, J6 Pin 7 
M77-> 
Y:$78A01,5,1 
Input 46 Data Line, J6 Pin 26 
M78-> 
Y:$78A01,6,1 
Input 47 Data Line, J6 Pin 8 
M79-> 
Y:$78A01,7,1 
Input 48 Data Line, J6 Pin 27 
M80-> 
Y:$078A02,0,1 
Output 17 Data Line 
12 
30 
M81-> 
Y:$078A02,1,1 
Output 18 Data Line 
13 
31 
M82-> 
Y:$078A02,2,1 
Output 19 Data Line 
14 
32 
M83-> 
Y:$078A02,3,1 
Output 20 Data Line 
15 
33 
M84-> 
Y:$078A02,4,1 
Output 21 Data Line  
16 
34 
M85-> 
Y:$078A02,5,1 
Output 22 Data Line 
17 
35 
M86-> 
Y:$078A02,6,1 
Output 23 Data Line 
18 
36 
M87-> 
Y:$078A02,7,1 
Output 24 Data Line 
19 
37 
Do not mix topologies, i.e., all sinking or all sourcing outputs.  If the common emitter is used, the 
common collector should be unconnected.  Conversely, if the common collector is used, the common 
emitter should be unconnected. 
Sourcin