MACRO-CPU Hardware Reference
 
HARDWARE RE-INITIALIZATION 
MACRO hardware reinitialization to factory defaults is enabled when the SW1 setting is set to 15 or F 
(hexidecimal) and the power is cycled at the MACRO Station. The only time the user would want to use a 
hardware reinitialization to factory defaults with the MACRO Station would be if the MACRO Station always 
powers up with a watchdog (typically if the ring clock at the Ultralite is different than the ring clock at the 
MACRO Station). Node 11 will be the only MACRO Station node enabled. Therefore the user will have to enable 
node 11 of the MACRO IC at the Ultralite to communicate to the MACRO Station. 
  
Ultralite Example: Servo nodes 0,1,4,5 enabled at Ultralite (I996=$0F8033)  
(A) The user would have to enable node 11, I996=$0F8833  
(B) Then user can reistablish communications with MS11,(MIvar) commands  
(C) Issue MS$$$***11 to ensure re-initialization  
(D) Issue MSSAVE11 command to save the factory defaults to the Station  
 
Turbo Ultralite Example: Servo nodes 0,1,4,5 enabled at Ultralite (I6841=$0F8033) 
(A) The user would have to enable node 11, I996=$0F8833 
(B) Then user can reistablish communications with MS11,(MIvar) commands 
(C) Issue MS$$$***11 to ensure re-initialization 
(D) Issue MSSAVE11 command to save the factory defaults to the Station 
 
 
 