MACRO-CPU Hardware Reference
 
FIRMWARE UPDATES 
Downloading new firmware to the MACRO Station is a simple process once the MACRO board is setup properly.  
To download new firmware to the MACRO station, the user must have the following items:   
5V power supply 
2 jumpers 
DB9 female to 10 pin header (any cable used for PMAC RS232 communications) 
PC at the DOS prompt. 
New firmware and necessary downloading batch files 
 
Make sure to power down the MACRO Station 
To download the software to the MACRO station, the user will first jumper the following E2 (1-2) and E1 (1-2).  
Wire the 5V power to the appropriate terminal on the MACRO station or plug into 3U Rack.   
Place the 10 pin header cable to the serial connection on the MACRO-station and place the other end to the 
COM1 port on the PC (the batch files were written for COM1 but could be modified if necessary).   
Goto the DOS prompt and create a directory called firmware and station (as an example). 
C:\firmware\station 
a:\copy *.* c:\firmware\station 
Go back to the c drive and type the following command 
c:\firmware\station\mcdwnld 
The firmware will be down loaded to the MACRO station.  Easy! 
 
     The PMAC Executive Software will soon have the capability of downloading the MACRO Station firmware in 
the Windows Operating Environment. 
(5) Place jumper E2 back to pins 2-3 and remove E1 jumper 
 
 
Please call the factory if you have any questions. 
 
 
 