131
Refer to the Analog Timer Unit’s Operation Manual for details on switching
between internal and external timer SV settings, connecting a variable resistor,
and switch settings.
Bits 08 to 11 of n
Timer Start Input
Completion Flags
Timer Set
Bits
(Bits 00 to
03 of n)
Time-up
Output
Timer Start Input
Time-up Output
Timer interval
4-13-2 Bit Allocation and DIP Switch Settings
The following table shows the use of the word (n) allocated to the Analog Timer
Unit. This word address depends upon the slot in which the Unit is mounted.
Bit
I/O class
Function
Comments
00
Output
Timer 0 Set Bit
ON when timer is set.
01
Timer 1 Set Bit
02
Timer 2 Set Bit
03
Timer 3 Set Bit
04
Timer 0 Stop Bit
OFF: Enable timer operation
05
Timer 1 Stop Bit
ON: Stop timer operation
06
Timer 2 Stop Bit
07
Timer 3 Stop Bit
08
Input
Timer 0 Completion Flag
ON when timer has timed out.
09
Timer 1 Completion Flag
10
Timer 2 Completion Flag
11
Timer 3 Completion Flag
12 to 15
---
Not used.
---
Timer Range Setting
Set the timer range with the upper DIP switch on the front of the Unit. Each tim-
er’s range can be set independently.
Range
Timer 0
Timer 1
Timer 2
Timer 3
Pin 8
Pin 7
Pin 6
Pin 5
Pin 4
Pin 3
Pin 2
Pin 1
0.1 to 1 s
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
1 to 10 s
ON
OFF
ON
OFF
ON
OFF
ON
OFF
10 to 60 s
OFF
ON
OFF
ON
OFF
ON
OFF
ON
1 to 10 minutes
ON
ON
ON
ON
ON
ON
ON
ON
Select internal or external setting with the lower DIP switch on the front of the
Unit.
Setting
Timer 0 (pin 4)
Timer 1 (pin 3)
Timer 2 (pin 2)
Timer 3 (pin 1)
Internal
ON
ON
ON
ON
External
OFF
OFF
OFF
OFF
Selecting Internal/External
Timer SV Setting
Analog Timer Unit Programming
Section 4-13