The following example shows how to use BSET(71) to change the PV of a timer
depending on the status of IR 00003 and IR 00004. When IR 00003 is ON, TIM
010 will operate as a 50-second timer; when IR 00004 is ON, TIM 010 will oper-
ate as a 30-second timer.
TIM 010
#9999
@BSET(71)
#0500
TIM 010
TIM 010
@BSET(71)
#0300
TIM 010
TIM 010
00004
00003
00003
00004
00004
00003
Address
Instruction
Operands
00000
LD
00003
00001
AND NOT
00004
00002
@BSET(71)
#
0500
TIM
010
TIM
010
00003
LD
00004
00004
AND NOT
00003
00005
@BSET(71)
#
0300
TIM
010
TIM
010
00006
LD
00003
00007
OR
00004
00008
TIM
010
#
9999
5-16-4
BLOCK TRANSFER – XFER(70)
N: Number of words (BCD)
IR, SR, AR, DM, HR, TC, LR, #
S: Starting source word
IR, SR, AR, DM, HR, TC, LR
Ladder Symbols
Operand Data Areas
D: Starting destination word
IR, SR, AR, DM, HR, TC, LR
XFER(70)
N
S
D
@XFER(70)
N
S
D
Limitations
Both S and D may be in the same data area, but their respective block areas
must not overlap. S and S+N must be in the same data area, as must D and D+N.
N must be BCD between 0000 and 6144.
Description
When the execution condition is OFF, XFER(70) is not executed. When the
execution condition is ON, XFER(70) copies the contents of S, S+1, ..., S+N to
D, D+1, ..., D+N.
2
D
3 4 5
1
D+1
3 4 5
2
D+2
3 4 2
2
D+N
6 4 5
2
S
3 4 5
1
S+1
3 4 5
2
S+2
3 4 2
2
S+N
6 4 5
Data Movement