Omron C200HE ユーザーズマニュアル

ページ / 564
235
5-19-9
BCD MULTIPLY – MUL(32)
Md: Multiplicand (BCD)
IR, SR, AR, DM, HR, TC, LR, #
Mr: Multiplier (BCD)
IR, SR, AR, DM, HR, TC, LR, #
Ladder Symbols
Operand Data Areas
R: First result word
IR, SR, AR, DM, HR LR
MUL(32)
Md
Mr
R
@MUL(32)
Md
Mr
R
Limitations
R and R+1 must be in the same data area.
Description
When the execution condition is OFF, MUL(32) is not executed. When the
execution condition is ON, MUL(32) multiplies Md by the content of Mr, and
places the result In R and R+1.
Md
Mr
R +1 
R
X
Example
When IR 00000 is ON with the following program, the contents of IR 013 and DM
0005 are multiplied and the result is placed in HR 07 and HR 08. Example data
and calculations are shown below the program.
MUL(32)
013
DM 0005
HR 07
00000
R+1: HR 08
R: HR 07
0
0
0
8
3
9
0
0
Md: IR 013
3
3
5
6
Mr: DM 0005
0
0
2
5
X
Address
Instruction
Operands
00000
LD
00000
00001
MUL(32)
013
DM
00005
HR
07
Flags
ER:
Md and/or Mr is not BCD.
Indirectly addressed DM word is non-existent. (Content of 
DM word is
not BCD, or the DM area boundary has been exceeded.)
EQ:
ON when the result is 0.
BCD Calculations
Section 5-19