Omron C200HE ユーザーズマニュアル

ページ / 564
477
PC Settings
PC Mode
UM Area
RUN
MONITOR
PROGRAM
Write-protected
Read-protected
OK
OK
OK
OK
---
Execution Conditions
Commands
Responses
Single
Multiple
Single
Multiple
OK
---
OK
---
End Codes
An end code of 04 (address over) will be returned if the program address is
above the highest program address but less than 65,536 (32,768 in the
C200HS).
An end code of 14 (format error) will be returned if the length of the command is
incorrect.
An end code of 15 (entry number data error) will be returned if the program ad-
dress exceeds the 65,535 maximum (32,767 in the C200HS), the program ad-
dress isn’t specified in BCD, or the mnemonic/SV operands are incorrect.
An end code of 16 (command not supported) will be returned if the specified
instruction doesn’t exist in the program.
End code
Contents
00
Normal completion
04
Address over
13
FCS error
14
Format error
15
Entry number data error
16
Command not supported
18
Frame length error
23
User memory protected
10-3-20
SV CHANGE 1 –– W#
Searches for the first instance of the specified TIM, TIMH(15), CNT, CNTR(12),
or TTIM(87) instruction in the user’s program and changes the SV to new
constant SV specified in the second word of the instruction.
Command Format
@
W
#
OP1 OP2 OP3 OP4
x 10
0
x 10
1
x 10
3
x 10
2
x 10
0
x 10
1
x 10
3
x 10
2
x 10
0
x 10
1
Node no.
Header
code
Mnemonic
Timer/counter
(0000 to 0511)
SV (0000 to 9999)
Terminator
FCS
Use all four characters to specify the timer or counter instruction’s mnemonic.
Add a space to the end of a TIM or CNT mnemonic to make it 4 characters long.
Instruction name
Mnemonic
TC number
OP1
OP2
OP3
OP4
range
TIMER
T
I
M
(Space) 0000 to 0511
HIGH-SPEED TIMER
T
I
M
H
COUNTER
C
N
T
(Space)
REVERSIBLE COUNTER
C
N
T
R
TOTALIZING TIMER
T
T
I
M
Host Link Commands
Section 10-3