Omron C200HE ユーザーズマニュアル

ページ / 564
481
Response Format
@
W
%
x 16
0
x 10
0
x 10
1
x 16
1
Node no.
Header
code
Terminator
FCS
End code
Limitations
The command is valid only when the UM setting is ladder only.
SR 253 through SR 255 can’t be specified.
The command can’t be executed if the UM area is write-protected.
PC Settings
PC Mode
UM Area
RUN
MONITOR
PROGRAM
Write-protected
Read-protected
---
OK
OK
---
OK
Execution Conditions
Commands
Responses
Single
Multiple
Single
Multiple
OK
---
OK
---
End Codes
An end code of 14 (format error) will be returned if the length of the command is
incorrect.
An end code of 15 (entry number data error) will be returned if the program ad-
dress isn’t BCD, the program address exceeds the maximum address in the pro-
gram, the mnemonic/TC number is incorrect, or the SV is incorrect.
An end code of 16 (command not supported) will be returned if the specified
instruction doesn’t exist in the program.
End code
Contents
00
Normal completion
01
Not executable in RUN mode
04
Address over
13
FCS error
14
Format error
15
Entry number data error
16
Command not supported
18
Frame length error
23
User memory protected
10-3-23
STATUS READ –– MS
Reads the PC operating conditions.
Command Format
@
M
S
x 10
0
x 10
1
Node no.
Header
code
Terminator
FCS
Response Format
@
M
S
x 16
2
x 10
0
x 10
1
x 16
1
x 16
0
x 16
3
x 16
0
x 16
1
Node no.
Header
code
Status data
End code
Terminator
FCS
Message
16 characters
Host Link Commands
Section 10-3