490
PC Settings
PC Mode
UM Area
RUN
MONITOR
PROGRAM
Write-protected
Read-protected
---
OK
OK
OK
OK
Execution Conditions
Commands
Responses
Single
Multiple
Single
Multiple
OK
---
OK
---
End Codes
An end code of 14 (format error) will be returned if the length of the command is
incorrect.
End code
Contents
00
Normal completion
13
FCS error
14
Format error
18
Frame length error
10-3-30
PC MODEL READ –– MM
Reads the model type of the PC. The codes returned for this command are differ-
ent from the NT Link codes.
Command Format
@
M
M
x 10
0
x 10
1
Node no.
Header
code
Terminator
FCS
Response Format
@
M
M
x 10
0
x 10
1
x 16
1
x 16
0
x 16
1
x 16
0
Node no.
Header
code
Terminator
FCS
End code
Model
code
“Model code” indicates the PC model in two digits hexadecimal.
Model code
Model
01
C250
02
C500
03
C120
0E
C2000
10
C1000H
11
C2000H/CQM1
12
C20H/C28H/C40H, C200H, C200HS, C200HX/HG/HE
20
CV500
21
CV1000
22
CV2000
40
CVM1-CPU01-E
41
CVM1-CPU11-E
42
CVM1-CPU21-E
PC Settings
PC Mode
UM Area
RUN
MONITOR
PROGRAM
Write-protected
Read-protected
OK
OK
OK
OK
OK
Host Link Commands
Section 10-3