Omron C200HE ユーザーズマニュアル

ページ / 564
55
3-5-13 Cycle Time Flag
AR 2405 turns ON when the cycle time set with SCAN(18) is shorter than the
actual cycle time.
AR 2405 is refreshed every cycle while the PC is in RUN or MONITOR mode.
3-5-14 Link Unit Mounted Flags
The following flags indicate when the specified Link Units are mounted to the
Racks. (Refer to 3-5-15 CPU Unit-mounting Device Mounted Flag for CPU Unit-
mounting Host Link Units.) These flags are refreshed every cycle.
Name
Bit
Link Unit
SYSMAC LINK/SYSMAC NET Link Unit
Level 1 Mounted Flag
AR 2408
SYSMAC LINK/SYSMAC NET Link Unit in operating level 1
SYSMAC LINK/SYSMAC NET Link Unit
Level 0 Mounted Flag
AR 2409
SYSMAC LINK/SYSMAC NET Link Unit in operating level 0
Rack-mounting Host Link Unit Level 1
AR 2413
Rack-mounting Host Link Unit in operating level 1
Rack-mounting Host Link Unit Level 0
AR 2414
Rack-mounting Host Link Unit in operating level 0
3-5-15 CPU Unit-mounting Device Mounted Flag
AR 2415 turns ON when any device is mounted directly to the CPU Unit. This
includes CPU Unit-mounting Host Link Units, Programming Consoles, and In-
terface Units. This flag is refreshed every cycle.
3-5-16 FPD Trigger Bit
AR 2508 is used to adjust the monitoring time of FPD(––) automatically. Refer to
5-25-12 FAILURE POINT DETECT – FPD(––) for details.
3-5-17 Data Tracing Flags and Control Bits
The following control bits and flags are used during data tracing with TRSM(45).
The Tracing Flag will be ON during tracing operations. The Trace Completed
Flag will turn ON when enough data has been traced to fill Trace Memory.
Bit
Name
AR 2512
Trace Completed Flag
AR 2513
Tracing Flag
AR 2514
Trace Trigger Bit (writeable)
AR 2515
Sampling Start Bit (writeable)
Note Refer to 5-25-3 TRACE MEMORY SAMPLING – TRSM(45) for details.
3-5-18 Cycle Time Indicators
AR 26 contains the maximum cycle time that has occurred since program execu-
tion was begun. AR 27 contains the present cycle time.
Both times are to tenths of a millisecond in 4-digit BCD (000.0 ms to 999.9 ms),
and are refreshed every cycle.
AR (Auxiliary Relay) Area
Section 3-5