Campbell Manufacturing RF415 ユーザーズマニュアル

ページ / 90
RF400 Series Spread Spectrum Data Radio/Modems
26
RF400
RF400
RF400
RF400
DATALOGGER
DATALOGGER
DATALOGGER
FIGURE 8.  Point-to-Multipoint System
5.3.4  PC208W Configuration
a.
Point-to-point
(1) Device Map -
COM1
CR10X1
(2) Set station CR10X1 baud rate to 9600 baud in network map
(3) Datalogger extra response time – 0 mS
b.
Point-to-multipoint
(1) Device Map -
COM1
Generic1
10X3001
10X3005
(2) Set Generic Modem baud rate to 9600 in device map.
(3) Generic Modem Settings
(a)
√ “Make DTR Active”
(b)
√ “Hardware Flow Control”
(c) Extra Response Time (Standby Mode Max Response Delay +
200 ms; see Table D-1)
(i) 0 mS with 24 mA Standby Mode
(ii) 1200 mS with 1/2 sec cycle default Standby Mode delay
(iii) 4200 mS with 2 sec cycle Standby Mode delay
6 dBd Yagi
CS I/O
CS I/O
CS I/O
CS I/O
9 dBd Yagi
CS I/O
CS I/O
0 dBd Half-wave
3 dBd Omni Collinear
RS-232
AC Adapter