E658130
- 26 -
2. Remote register (Inverter -> Master)
RWr
Address Signal
Description
RWr n
Monitor value 1
When (RYnC) is on, the monitored value specified to the lower 8 bits of
the monitor code (RWwn) is set.
the monitor code (RWwn) is set.
RWrn+1
Monitor value 2
(output frequency)
When "0" is set to the higher 8 bits of the monitor code (RWwn), the
current output frequency is always set. When other than "0" is set to the
current output frequency is always set. When other than "0" is set to the
upper 8 bits of the monitor code (RWwn) and (RYnC) is on, the
monitored value specified to the higher 8 bits of the monitor code
(RWwn) is set.
(RWwn) is set.
RWrn+2
Response code 1
When (RYnF) is on, the response code correspond to the instruction
code of (RWwn+2) is set. The value "0" is set for a normal reply and
other than "0" is set for data fault, mode error, etc.
code of (RWwn+2) is set. The value "0" is set for a normal reply and
other than "0" is set for data fault, mode error, etc.
RWrn+3
Read data 1
For a normal reply, the reply data to the instruction specified by the
instruction code is set.
instruction code is set.
RWrn+4
Monitor value 3
When (RYnC) is on, the monitored value specified to the monitor code
(RWw n+4) is set.
(RWw n+4) is set.
RWrn+5
Monitor value 4
When (RYnC) is on, the monitored value specified to the monitor code
(RWw n+5) is set.
(RWw n+5) is set.
RWrn+6
Monitor value 5
When (RYnC) is on, the monitored value specified to the monitor code
(RWw n+6) is set.
(RWw n+6) is set.
RWrn+7
Monitor value 6
When (RYnC) is on, the monitored value specified to the monitor code
(RWw n+7) is set.
(RWw n+7) is set.
RWrn+8
Trip information
(Trip code)
The fault data of the trip history No. specified by (RWw n+8) is stored in
the lower 8bits.
The trip history No. specified is echo backed to the upper 8bits.
the lower 8bits.
The trip history No. specified is echo backed to the upper 8bits.
RWrn+9
Trip information
(output frequency)
Output frequency of the trip history No. specified in (RWw n+8) is
stored.
stored.
RWrn+A
Trip information
(output current)
Output current of the trip history No. specified in (RWw n+8) is stored.
RWrn+B
Trip information
(output voltage)
(output voltage)
Output voltage of the trip history No. specified in (RWw n+8) is stored.
RWrn+C
Trip information
(energization time)
Energization time of the trip history No. specified in (RWw n+8) is
stored.
stored.
RWrn+D
to
RWrn+F
Reserved
Do not use it.
RWrn+10
Reply code 2
When (RYnF) is on, the response code correspond to the instruction
code of (RWw n+10) is set. The value "0" is set for a normal reply and
other than "0" is set for data fault, mode error, etc.
code of (RWw n+10) is set. The value "0" is set for a normal reply and
other than "0" is set for data fault, mode error, etc.
RWrn+11
Read data 2
For a normal reply, the reply data to the instruction specified by the
instruction code is set.
instruction code is set.
RWrn+12
Reply code 3
When (RYnF) is on, the response code correspond to the instruction
code of (RWw n+12) is set. The value "0" is set for a normal reply and
other than "0" is set for data fault, mode error, etc.
code of (RWw n+12) is set. The value "0" is set for a normal reply and
other than "0" is set for data fault, mode error, etc.