E658130 
- 28 - 
5.5.8.  Instruction Codes 
 
Code No. 
Item 
Description 
1003H 
Command mode selection   
read 
2003H 
Command mode selection   
write 
0: Terminal block 
1: Panel keypad (including extension panel) 
2: RS485 communication 
3: No function 
4: Communication option 
1004H 
Frequency setting mode   
selection read 
2004H 
Frequency setting mode   
selection write 
0: Setting dial 1(save even if power is off) 
1: Terminal VIA 
2: Terminal VIB 
3: Setting dial 2(press in center to save) 
4: RS485 communication 
5: UP/DOWN from external logic input 
6: No function 
7: Communication option 
8: Terminal VIC 
9, 10: - 
11: Pulse train input 
12, 13: -   
14: sro 
0072H Special 
monitor 
0000H to FFFFH: 
Monitor value selected after choosing instruction code 00F3H. 
read 0073H Special monitor code read 
Read the content that was monitored by special monitor. 
write 00F3H Special monitor selection 
Select the monitor code of special monitor. 
0074H 
Trip history No.1, No.2 read 
Read the No.1 and No.2 of trip information. 
0075H 
Trip history No.3, No.4 read 
Read the No.3 and No.4 of trip information. 
0076H 
Trip history No.5, No.6 read   
Read the No.5 and No.6 of trip information. 
0077H 
Trip history No.7, No.8 read 
Read the No.7 and No.8 of trip information. 
006DH 
Frequency command value   
(RAM) read 
Read the frequency command value (RAM). 
00EDH 
Option frequency command   
value (EEPROM&RAM) write*
Write the option frequency command value (EEPROM &RAM).
00F4H 
Trip history clear 
9696H: Clear all trip histories. 
00FCH 
Parameter all clear 
9696H: Clear all parameters. (Parameters other than   
proofreading values are made into factory default settings.) 
00FDH 
Inverter reset 
9696H: Reset the inverter. 
1000H to 1999H 
(1000H to 
1F99H) 
Read parameters (RAM) 
To read parameters f000 to f984, add the triple figures 
that follow Fxxx to 1000H.   
(Ex: f984 -> 984 + 1000 = 1984)   
No error occurs when you select 1A00 to 1F99.   
Because these parameters are for maintenance.   
2000H to 2999H 
Write parameters   
(EEPROM&RAM) * 
To write parameters f000 to f984, add the triple figures 
that follow Fxxx to 2000H.