Troubleshooting Using Indicators
Section 9-1
Data Link Cannot be 
Stopped
Stopping the data link depends on the Controller Link Unit operating normally
and participating in the Network. Read the above explanations before
attempting to stop operation.
Note Stop the data link from the node at which the LNK indicator is lit (indicating
active data links). Data links cannot be stopped from nodes which do not have
active data links.
9-1-3
CVM1 and CV-series Controller Link Units
Troubleshooting with RUN, ERC, ERH and INS Indicators
The RUN, ERC, ERH and INS indicators can be used to check whether Con-
troller Link Unit startup and Network participation are operating normally.
Note Be sure to turn off the power to the PLC before performing any of the follow-
ing.
• Disconnecting the Unit or connectors.
• Securing Units or connectors.
Indicators
Probable cause
Probable remedy
LNK
M/A
Lit
---
Data link operating normally.
---
Flashing
Lit
When manual setting is used, 
there is an error in the data link 
table.
Refer to 5-2-2 Manual Setting 
and remake the data link table.
Flashing
Not lit
When automatic setting is 
used, the data link parameters 
at the startup node are incor-
rect for the local node (the 
data link area is out of range 
for the local node.)
Refer to 5-2-4 Automatic Set-
ting
, r
eset the parameters for 
the startup node DM Area so 
that the local node can partici-
pate in the data link, and then 
restart the data link.
Automatic setting is used with 
1:N allocations, but the device 
does not support this function.
Use a Controller Link Unit that 
supports automatic data link 
creation with 1:N allocations. 
Refer to Automatic Setting on 
page 129 for details.
Not lit
Lit
When manual setting is used, 
there are no data link tables 
set for the local node.
Set data link tables for the 
local node.
Not lit
Not lit
When automatic setting is 
used, the startup node is not 
set to participate in the data 
links.
Stop the data links, remake 
and set the parameters in the 
startup node’s DM Area, and 
then restart the data link.
RUN
ERC
INS
SD
ERH
LNK
RD
TER
M/A
  CLK21
RUN: Operating
ERC: Communications 
error
INS: Network 
participation
LNK: Data 
link
M/A: 
Data link mode