Troubleshooting Using Indicators
Section 9-1
Indicators
Probable cause
Probable remedy
RUN
ERC
ERH
INS
Lit
---
---
Not lit Terminating resistance is 
not set correctly.
Turn ON the terminating 
resistance at the nodes at 
both ends of the Network 
and turn it OFF at all other 
nodes.
Cables are not connected 
correctly.
Check the cable connec-
tions and reconnect cor-
rectly.
The node address is larger 
than the maximum node 
address set for the network 
parameters.
Either reset the maximum 
node address using the 
Controller Link Support 
Software or reset the node 
address to below the maxi-
mum.
No other nodes exist.
Make sure that 2 or more 
nodes exist within the Net-
work.
No nodes have been set as 
polling nodes.
Refer to 8-1-2 Setting the 
Polling and Polled Nodes
 
and set at least one polling 
node. (Controller Link 
Units should normally be 
set as polling nodes.)
The set baud rate is differ-
ent to other nodes (Wired 
Unit).
Refer to SECTION 4 Prep-
arations for Communica-
tions
 and set all nodes on 
the network to the same 
baud rate.