Omron CJ1W-CLK21-V1 ユーザーズマニュアル

ページ / 401
322
Troubleshooting Error Messages in CX-Net Data Link Table Check
Section 9-4
The 
XX
 symbol refers to the corresponding node address. The two
asterisks (**) refer to the corresponding area type, address, and number of
words. 
Node XX Dest Over-
flow 
Warning: Overflow occurred
The number of receive words at the destination node is 
larger than the number of send words at the source node. 
Change the number of send words or number of receive 
words if the allocations are not intended. If the allocations 
are intended, the data link tables can be transmitted without 
making any changes. 
Warning: Block outside bounds of 
Link from node **. Enter value in 
range ** to **
The number of receive words at the destination node is 
smaller than the number of send words at the source node. 
Change the number of send words or number of receive 
words if the allocations are not intended. If the allocations 
are intended, the data link tables can be transmitted without 
making any changes. 
Node XX Node size 
Warning: The total node send 
and receive size of ** exceeds 
12000
The total number of send and receive words exceeds 
12,000. Controller Link Units with unit version 1.2 or later are 
required for data links with 20,000 send and receive words. 
For pre-Ver. 1.2 Controller Link Units, reduce the number of 
send and receive words.
Total Node send size of ** 
exceeds max 20000
The total number of send and receive words exceeds 
20,000. Reduce the number of send and receive words to 
within the maximum.
Total Node send size of ** 
exceeds max 8000
The total number of send and receive words exceeds 8,000. 
Reduce the number of send and receive words to within the 
maximum.
Total Node send size of ** 
exceeds max 62000
The total number of send and receive words exceeds 
62,000. Reduce the number of send and receive words to 
within the maximum. (The 62,000 maximum can be 
exceeded by personal computer boards only.)
Total Node send size is 0 
The number of allocated words for node ** in node No. xx is 
0. Change the number of words or delete the node.
Total Node send size of ** 
exceeds max 1000
The total number of send words for node XX exceeds 1,000. 
Set the number of send words to 1,000 words or less. 
Node XX Area Overlap
Node XX Area Conflict
Warning: Duplicated area exists 
in Area 1 and status area
The same words have been allocated for both the Data Link 
Area 1 and status area. If the duplication is not intended, 
change the settings for either area. If the duplication is 
intended,   the data link tables can be transmitted without 
making any changes. 
Warning: Duplicated area exists 
in Area 2 and status area
The same words have been allocated for both the Data Link 
Area 2 and status area. If the duplication is not intended, 
change the settings for either area. If the duplication is 
intended,   the data link tables can be transmitted without 
making any changes. 
Warning: Link memory areas 1 
and 2 are both set to - [Area]
The same area has been set for both Data Link Area 1 and 
2. The same area can be set if using Controller Link Units 
with unit Ver. 1.2 or later. If a pre-Ver. 1.2 Controller Link Unit 
is being used, set a different area each for Area 1 and Area 
2. (This message is displayed for CS/CJ-series CPU Units 
only.) 
Link memory areas 1 and 2 are 
both set to [Area]
The same area has been set for both Data Link Area 1 and 
2. Set a different area each for Area 1 and Area 2. (This mes-
sage is displayed for CS/CJ-series CPU Units only.)
Link memory areas 1 and 2 are 
both set to [Area]
The same address has been set for the Data Link Area and 
the area in which both Area 1 and Area 2 are set. Reset the 
addresses so that no duplication occurs. (This message is 
displayed for CS/CJ-series CPU Units only.)
Error message
Troubleshooting