Cleaning and Inspection
Section 9-5
9-5
Cleaning and Inspection
This section describes cleaning and inspection procedures that are to be per-
formed as daily maintenance.
9-5-1
Cleaning
Conduct the following periodic cleaning to keep the Controller Link Unit in
optimum condition.
• Wipe the Unit with a dry, soft cloth daily.
• For stains that cannot be removed with a dry cloth, dip the cloth in
medium strength alcohol (2%), wring the cloth tightly, and then wipe down
the Unit.
• If glue, vinyl, or tape is left on the Unit for long periods of time, it will stain.
Remove these items during cleaning.
!Caution
Do not use volatile solvents such as benzine or paint thinner, or chemical
cloths for cleaning. They will damage the quality of the coating on the Unit.
9-5-2
Inspection
Controller Link Units must be inspected on a regular basis to ensure correct
operation. Inspections should be conducted once every 6 to 12 months. If the
Unit is subject to extremes in temperature or humidity, inspections should be
conducted on a more regular basis.
Tools and Equipment Need for Inspection
The following tools and equipment will be needed to perform inspection and
adjustments.
• Assorted flat-blade and Phillips screwdrivers
• Circuit tester or digital voltmeter
• Industrial-grade alcohol and clean cotton cloth
• Synchroscope
• Pen-chart recording oscilloscope
• Thermometer, hygrometer
Inspection Items
Inspect the follow items to see if they deviate from the prescribed standards. If
any items do deviate from the standard either adjust so they are within the
operating range or adjust the Unit accordingly.
Item
Description
Inspection instrument
Ambient condi-
tions
Temperature: 0
°
 to 55
°
C
Thermometer
Humidity: 10% to 90% (no conden-
sation or freezing)
Hygrometer
Dust-free
Sight
Installation
Units securely attached?
Communications cable connectors 
tight?
Communications cabling used for 
external wiring intact (no breaks)?
Flat-blade screwdriver and 