Omron CJ1W-CLK21-V1 ユーザーズマニュアル

ページ / 401
34
Data Links Procedures
Section 2-1
8.
Start the data links.
Note a) Data link Start/Stop Bit (N= unit number):
CS/CJ Series:
Word 0 of DM30000 + 100 
×
 N 
C200HX/HG/HE:
AR 0700 (operating level #0), 
AR 0704 (operating level #1)
CVM1/CV Series: 
Word 0 of DM 2000 + 100 
×
 N 
CQM1H Series:
AR 0700
b) The data links will not start if there is an error in the data link
tables in the startup node.
9.
Stop the data links.
Note Data link Start/Stop Bit (N= unit number):
CS/CJ Series:
Word 0 of DM30000 + 100 
×
 N 
C200HX/HG/HE:
AR 0700 (operating level #0), 
AR 0704 (operating level #1)
CVM1/CV Series:  Word 0 of DM 2000 + 100 
×
 N 
CQM1H Series:
AR 0700
2-1-2
Automatically Setting Data Links
Data link tables can be automatically created by setting the data link mode to
automatic data link table creation. Use the following procedure.
1,2,3...
1.
Install and wire the Units.
Contents
Method
Nodes
Page
Start the data links.
Switch the Data link 
Start/Stop Bit (listed 
below) from OFF to 
ON using either the 
Programming Device, 
the user program, the 
Controller Link Sup-
port Software or CX-
Programmer.
Data link startup node 
(The Start Bit can be 
turned ON in more 
then one node to 
make sure the data 
links start even when 
the startup node is 
down.)
Contents
Method
Nodes
Page
Stop the data links.
Switch the Data link 
Start/Stop Bit (listed 
below) from OFF to 
ON using either the 
Programming Device, 
the user program, the 
Controller Link Sup-
port Software or CX-
Programmer.
Any node that is active 
in the data link 
Contents
Method
Nodes
Page
a. Mount the Units to 
the PLCs.
---
All nodes
b. Wire the Network.
---
All nodes