Omron CJ1W-CLK21-V1 ユーザーズマニュアル

ページ / 401
36
Data Links Procedures
Section 2-1
Note a) When using fewer than 33 nodes, make sure that the Wired Net-
work 62 Node Enable Bit if the DM Parameter Area software
switch is turned OFF to restrict the network to 32 nodes maximum.
To construct a network containing more than 32 nodes, all nodes
must use the CS1W-CLK21-V1 or CJ1W-CLK21-V1.
b) Be sure that the data link mode in the data link parameters in the
DM Area is set to 00 when using manually set data links.
c) When using the 8-bit storage format, make sure that the relevant
locations in the DM Parameter Area are set to 0. The storage for-
mat used by all models other than CS1W-CLK21-V1, CS1W-
CLK21, CJ1W-CLK21-V1, and CJ1W-CLK21 is fixed at 8-bit, re-
gardless of the setting.
7.
Set the parameters for automatic data link creation.
• Equality layout: Previous automatic creation method (Compatible with
CS1W-CLK21-V1, CJ1W-CLK21-V1, CS1W-CLK21, CJ1W-CLK21,
C200HW-CLK21, CVM1-CLK21, and CQM1H-CLK21)
Contents
Method
Nodes
Page
a.  Set the data link mode 
to automatic. 
Use the Support 
Software or Pro-
gramming Console.
Data link startup node 
only
The node that is used 
to start the data link is 
called the startup 
node. It is necessary 
to decide beforehand 
which node will be 
the startup node.
Area 
1
b.  Set the area
Data link startup node 
only
Only when Area 1 is 
used
c. Set the data 
link start word 
d.  Set the num-
ber of data link 
words
Area 
2
e.  Set the area
Data link startup node 
only
Only when Area 2 is 
used
f.  Set the data 
link start word 
g.  Set the num-
ber of data link 
words
h.  Set the first data link 
status word
Data link startup node 
only
(This setting may be 
omitted.)
i.  Set the nodes to par-
ticipate in the data 
links.
Data link startup node 
only