Zhone Technologies Z-PLEX-10-24-DOC-SC ユーザーズマニュアル

ページ / 101
4-6 \ 
Zhone Technologies
Model No.
Running Head
Configuring SNMP
Configuring the Z-Plex
The following example configures the IP over FDL interface:
user> SET CPUCFG:MASKFDL:1:255.255.255.252
user> SET CPUCFG:IPFDL:1:192.168.8.22
For most applications, the default MTU of 1500 is appropriate. If you need to change it, use 
the MTUFDL command as in the following example:
user> SET CPUCFG:MTUFDL:1:1200
4.2.4
Configuring system contact information
The following example configures system contact and description information:
user> SET SYSTEM:SYSCONTACT:Scott_Berman
user> SET SYSTEM:SYSNAME:ZPlex-10-2-1
user> SET SYSTEM:SYSLOCATION:10th_flr-rack_2-unit1
4.3
Configuring SNMP
You can configure the Z-Plex unit using SNMP as well as specify SNMP trap recipients. The 
Z-Plex sends traps when the following major alarms occur: resets, red alarms, or yellow 
alarms. 
To configure SNMP on the Z-Plex you must:
Configure the IP addresses of the SNMP trap recipients
Specify SNMP community strings
Specify whether traps are enabled
The following example configures SNMP on the Z-Plex unit: 
1. Configure SNMP read/write and read community strings:
user> SET CPUCFG:RDCOMSTRING:1:publicpassword
user> SET CPUCFG:WTCOMSTRING:1:2Ws34rt
2. Enable SNMP traps (if necessary):
user> SET CPUCFG:SNMPTRAP:1:ON
3. Configure up to 3 SNMP traps recipients (if necessary):
user> SET CPUCFG:IPHOST1:1:192.168.21.23