Communications Installation - RS-485 Link to Operator Interface 
102 
  HC900 Hybrid Controller Installation and User Guide 
Revision 5 
  
9/03 
Step Procedure 
Select the Set Controller’s Network Parameters button.   Using the wizard (bottom radio button), 
select the PC port to be used, then set the controller’s new network parameters including IP address, 
Subnet Mask (if other than the default), and Default Gateway IP address (if required, otherwise use 
default). Refer to the HC900 Hybrid Control Designer User’s Guide or its respective on-line help, 
Utilities Worksheet - Set Controller’s Network Parameters, for further details on this step.  
Note: This step will require the controller to be placed temporarily in the Program mode.  After the 
new network parameters have been downloaded, the controller will conduct a Cold Start in its 
transition to RUN. This will cause an initialization if there is a current configuration in the controller.