Monitoring and Operating the Controller 
4/07 
UDC2500 Universal Digital Controller Product Manual 
115 
4.17   Setting Failsafe Mode 
Introduction 
You can set the Failsafe Mode to be Latching or Non-Latching. 
Set Failsafe Mode 
Table 4-23  Procedure for Setting a Failsafe Mode  
Step 
Operation 
Press 
Result 
Select Control  
Set-up Group 
Setup
Setup
 
Until you see: 
Upper Display
 = SET  
Lower Display = CONTRL 
Select Failsafe 
Function Prompt 
Function
Function
Function
 
You will see: 
Upper Display =  
  LACH (Controller goes to manual and output goes to  
  
failsafe 
value) 
 NO 
(Controller mode does not change and output goes 
   
to failsafe value) 
Lower Display = FSMODE 
Select a value 
or
 
To select a failsafe mode in the upper display. 
Return to Normal 
Display 
Lower
Display
Lower
Display
Lower
Display
 
At power up, the output will go to the value set. 
 
4.18  Setpoint Rate/Ramp/Program Overview 
Introduction 
The Setpoint Ramp configuration group lets you enable and configure any of the 
following: 
•  SPRATE – a specific rate of change for any local setpoint change.  (Subsection 4.20) 
•  SPRAMP – a single setpoint ramp that occurs between the current local setpoint and 
a final local setpoint over a time interval of 1 to 255 minutes.  (Subsection 4.19) 
•  SPPROG – a ramp/soak profile in a 12-segment program. (Subsection 4.21) 
This section explains the operation of each selection and configuration reference where 
necessary. 
PV Hot Start 
This is a standard feature.  At power-up, the setpoint is set to the current PV value and 
the Rate or Ramp or Program then starts from this value.