Honeywell UDC2500 ユーザーズマニュアル
Monitoring and Operating the Controller
4/07
UDC2500 Universal Digital Controller Product Manual
115
4.17 Setting Failsafe Mode
Introduction
You can set the Failsafe Mode to be Latching or Non-Latching.
Set Failsafe Mode
Table 4-23 Procedure for Setting a Failsafe Mode
Step
Operation
Press
Result
1
Select Control
Set-up Group
Setup
Setup
Until you see:
Upper Display = SET
Upper Display = SET
Lower Display = CONTRL
2
Select Failsafe
Function Prompt
Function
Function
Function
You will see:
Upper Display =
LACH (Controller goes to manual and output goes to
Upper Display =
LACH (Controller goes to manual and output goes to
failsafe
value)
NO
L (Controller mode does not change and output goes
to failsafe value)
Lower Display = FSMODE
3
Select a value
or
To select a failsafe mode in the upper display.
4
Return to Normal
Display
Lower
Display
Lower
Display
Lower
Display
At power up, the output will go to the value set.
4.18 Setpoint Rate/Ramp/Program Overview
Introduction
The Setpoint Ramp configuration group lets you enable and configure any of the
following:
following:
• SPRATE – a specific rate of change for any local setpoint change. (Subsection 4.20)
• SPRAMP – a single setpoint ramp that occurs between the current local setpoint and
• SPRAMP – a single setpoint ramp that occurs between the current local setpoint and
a final local setpoint over a time interval of 1 to 255 minutes. (Subsection 4.19)
• SPPROG – a ramp/soak profile in a 12-segment program. (Subsection 4.21)
This section explains the operation of each selection and configuration reference where
necessary.
necessary.
PV Hot Start
This is a standard feature. At power-up, the setpoint is set to the current PV value and
the Rate or Ramp or Program then starts from this value.
the Rate or Ramp or Program then starts from this value.