Monitoring and Operating the Controller 
4/07 
UDC2500 Universal Digital Controller Product Manual 
117 
Step 
Operation 
Press 
Result 
End the Ramp 
When the final setpoint is reached, “RUN” changes to 
“HOLD” in the upper display and the controller operates 
at the new final setpoint. 
Disable SPRAMP 
details. 
 
Power Outage 
If power is lost during a ramp, upon power-up the controller will be in HOLD and the 
setpoint value will be the setpoint value prior to the beginning of the setpoint ramp. 
The ramp is placed in hold at the beginning. 
Configure the mode at Set Up Group “CONTROL”, function prompt “PWRUP”.  See 
Subsection 3.11 – CONTRL GROUP FUNCTION Prompts. 
4.20 Setpoint  Rate 
Introduction 
When you have configured a SETPOINT RATE, it will apply immediately to local 
setpoint change. 
Configuration check 
Make sure: 
•  SPRATE is enabled 
•  SP RATE and SPPROG are not running. 
•  A Rate Up (EUHRUP) or Rate Down (EUHRDN) value has been configured in 
Engineering units per hour.   
ATTENTION 
A value of 0 will imply an immediate change in setpoint, that is, NO RATE applies.  See 
Subsection 3.5 – Configuration group “SPRAMP”
 for details.) 
Operation 
When a change to local setpoint is made, this controller will ramp from the original 
setpoint to the “target” setpoint at the rate specified. 
The current setpoint value can be viewed at Sn on the lower display. 
Power outages 
If power is lost before the “target” setpoint is reached, upon power recovery, the 
controller powers up with Sn = Current PV value and it automatically “Restarts” from Sn 
= current PV value up to the original “target” setpoint.